What each one actually is
RS-485 (formally TIA/EIA-485-A) is a physical-layer standard only: it specifies a differential pair (lines A and B), electrical levels, and common-mode range, but no protocol, no frame format and no connector. It is normally paired with a higher-level protocol such as Modbus, Profibus, Interbus or BACnet.
CAN (Controller Area Network, ISO 11898) is a full protocol: it defines message framing, a unique priority identifier per message, and how the bus itself decides which node gets to transmit when several try at once.
Reach, wiring and multi-drop
RS-485 links can run up to about 4000 feet (roughly 1200 m) over a single twisted pair, with multiple drivers and receivers on the same bus and a wide common-mode range that tolerates ground-potential differences between nodes.
How access to the bus is decided
RS-485 itself has no arbitration: whatever protocol runs on top of it (e.g. Modbus RTU) decides who talks when, typically with a single master polling slaves.
CAN arbitrates in hardware, bit by bit, every time two or more nodes start transmitting together. Each node sends its identifier bit by bit while reading the bus: a node sending a recessive bit (logical 1) that reads back a dominant bit (logical 0) immediately stops transmitting, because a higher-priority (lower-identifier) message is present. This lets the highest-priority message win the bus with no collision and no lost data, and every other node simply waits for the bus to free up.
CAN bit timing is built from four programmable segments per bit — Sync, Prop, Phase 1 and Phase 2 — measured in Time Quanta derived from the node's oscillator; per ISO 11898-1 the total bit time spans 8 to 25 time quanta, and it must not be shorter than the round-trip signal propagation time across the network for arbitration to work correctly.
Data rate
TIA/EIA-485-A allows data rates up to 10 Mbps, though most real RS-485 devices run well below that; they are not required to meet the full range or the 10 Mbps ceiling.
Typical applications
RS-485 is common in process control networks, industrial automation, remote terminal units, building automation (HVAC, security systems), and motor and motion control — anywhere a simple, long-distance multi-drop link is paired with an existing protocol.
CAN is the standard choice where several nodes must share a bus without a designated master and need deterministic, priority-based access — the reason it underpins most automotive and many industrial embedded networks.
Selection considerations
Choose RS-485 when the application already has (or wants) a simple master/slave protocol such as Modbus RTU, needs long cable runs, and does not need bus-level arbitration between many peer nodes.
Choose CAN when several nodes must transmit as peers, message priority matters, and the network needs built-in, collision-free arbitration rather than relying on a protocol layered on top of a plain differential pair.