FREE ENGINEERING CALCULATOR FORMULA SHOWN AUTOMATION

Calculateur de Timing Silence Modbus RTU (T1.5 / T3.5)

Compute the inter-character (T1.5) and inter-frame (T3.5) delays required by Modbus RTU for a baud rate.

Input parameters

Calculation results

Délai Inter-Trame (T3.5) 4010.4 µs
Délai Inter-Caractère (T1.5) 1718.8 µs
Temps d’un Caractère (11 bits) 1145.83 µs

The results update as soon as a value changes. They are indicative: check the assumptions below before sizing.

Receive this calculation by e-mail inputs, results, formula and assumptions, to keep in your design file

Information and useful resources

Method and formula

Au-dessus de 19200 bauds, la spec Modbus fixe T1.5 = 750µs et T3.5 = 1.75ms quel que soit le débit. En dessous, T1.5 = 1.5 × temps caractère et T3.5 = 3.5 × temps caractère (1 caractère = 11 bits en trame RTU standard).

Assumptions and validity

  • Trame RTU standard (11 bits par caractère : start + 8 data + parité/stop)
  • Conforme à la spécification officielle Modbus.org "MODBUS over Serial Line"

All the tools

24 free engineering calculators: power, RF, connectivity, conversion and automation.

Add this calculator to your site free, copy and paste this code