BH-485 online pH electrode with RS485 Modbus RTU digital output, designed for continuous pH measurement in industrial water and effluents.
Measure rangepH: 0.0~14.0; Temperature: (0~50.0)℃
Parameter measurementpH, Temperature
AccuracypH: ±0.1pH; Temperature: ±0.5℃
Cable LengthCan be ODM depend on user’s requirements
Communication modeRS485(Modbus RTU)
Housing MaterialABS
Product overview
Overview. The BOQU BH-485 digital pH sensor is an online pH electrode with RS485 output using the Modbus RTU protocol, designed for continuous pH measurement in industrial water and effluents.
Main characteristics. The pH measuring range is 0.0 to 14.0, with a resolution of 0.01 pH and an accuracy of ±0.1 pH. Temperature is measured from 0 to 50.0 ℃, with a resolution of 0.1 ℃ and an accuracy of ±0.5 ℃. A built-in temperature sensor provides automatic temperature compensation. The imported composite electrode automatically recognises standard solutions.
Interfaces and connectivity. The RS485 Modbus RTU output allows connection to sensor networks or PLCs, with a range of up to 500 m according to the manufacturer. Electrode parameters can be set and the electrode calibrated remotely.
Power and environment. The sensor operates from 12 to 24 V DC, with a power dissipation of 1 W. The housing is made of ABS and the overall size is 230 mm × 30 mm. The cable length can be customised according to user requirements.
Installation. The sensor suits immersion, pipeline and circulation installations.
No published question about this part yet. Questions are reviewed before publication.
Complete specifications
Every characteristic recorded for DIGITAL-PH-SENSOR-MODBUS-RTU-RS485, with where it comes from. Use the filters to find one quickly.
All specifications (11)
Characteristic
Value
Accuracy
pH: ±0.1pH; Temperature: ±0.5℃
Cable Length
Can be ODM depend on user’s requirements
Communication mode
RS485(Modbus RTU)
Housing Material
ABS
Installation
Sinking type, pipeline, circulation type etc.
Measure range
pH: 0.0~14.0; Temperature: (0~50.0)℃
Overall size
230mm×30mm
Parameter measurement
pH, Temperature
Power dissipation
1W
Power supply
12~24V DC
Resolution
pH: 0.01pH; Temperature: 0.1℃
No specification matches.
Last verification : 2026-11-02
Applications and use cases
Architectures in which DIGITAL-PH-SENSOR-MODBUS-RTU-RS485 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
A proprietary PLC locks the project into one vendor’s tools. Industrial controllers built on the Raspberry Pi Compute Module run Linux, Node-RED, Python or CODESYS on DIN rail, with I/O modules, an operator panel and a cellular router for remote access
Answers to the questions that the recorded characteristics of DIGITAL-PH-SENSOR-MODBUS-RTU-RS485 can answer. A question is not asked when nothing is recorded to answer it.
1Does it support RS-485?
Yes — recorded under "Communication mode": RS485(Modbus RTU).
2Does it support CAN bus?
Yes — recorded under "Cable Length": Can be ODM depend on user’s requirements.
3Does it support Modbus?
Yes — recorded under "Communication mode": RS485(Modbus RTU).
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details