The Chntek QTC403-L device provides remote monitoring of water pressure (0 ~ 1.6MPa), flow, and temperature in fire hydrants via NB-IoT wireless communication. Rated IP68, it runs on a 3.6V lithium battery pack.
Temperature range-25℃ ~ +85℃
Temperature measurement range-25.0℃~ +85.0℃, error: ± 2℃
Water pressure measurement range0 ~ 1.6MPa
Maximum power consumption0.165W
Power consumptionStandby power consumption
Pressure Sensor Accuracy0.5%FS
Product overview
Overview. The Chntek QTC403-L intelligent fire hydrant monitoring device is engineered for water pressure and flow monitoring in fire fighting pipe networks, pumping stations, and water supply pipelines without mains power. Utilizing a micro-power design (0.165W maximum power consumption), it remotely transmits pressure, accumulated flow, temperature, and battery status to a management platform via the NB-IOT TCP/IP wireless protocol.
Measurement performance. The unit measures water pressure across a 0 ~ 1.6MPa range with a 0.5%FS sensor accuracy, ± 0.5%FS/year stability, and >2 times overload pressure rating. Cumulative flow accuracy when the hydrant is fully opened is ≤± 5%, while temperature measurement spans -25.0℃~ +85.0℃ with a ± 2℃ error.
Operation and battery life. Data collection runs once every 1 minute with a default upload cycle every 6 hours (remotely configurable), supported by timing, alarm, vibration, and tilt wake-up methods. Powered at Vcc = 3.2± 0.4 VDC by a >12000mAH 3.6V lithium battery pack, the device achieves a service life of ≥ 5 years.
Construction and protection. Built from nylon and glass fiber for 150 caliber installations (outer diameter 280.0X inner diameter 150.0X height 40.0mm), the QTC403-L features IP68 ingress protection and ESD immunity of ± 4kV air and ± 2kV contact.
The Chntek QTC403-L device provides remote monitoring of water pressure (0 ~ 1.6MPa), flow, and temperature in fire hydrants via NB-IoT wireless communication. Rated IP68, it runs on a 3.6V lithium battery pack.
Temperature range-25℃ ~ +85℃
Temperature measurement range-25.0℃~ +85.0℃, error: ± 2℃
Water pressure measurement range0 ~ 1.6MPa
Maximum power consumption0.165W
Power consumptionStandby power consumption
2. Datasheet extract (recorded values)
Parameter
Value
Calibration method
Local accuracy correction
Commodity ID
1448249790033448960
Commodity name
QTC403-L Fire Hydrant Intelligent Monitoring Device
Communication method/protocol
NB-IOT TCP/IP protocol
Data collection cycle
Backstage inspection once every 1 minute
Data upload cycle
Upload data every 6 hours by default (can be modified remotely)
ESD characteristics
Air ± 4kV; contact ± 2kV without damage, no impact on accuracy
Flow accuracy
The fire hydrant is fully opened, and the cumulative error is ≤± 5%
Maximum power consumption
0.165W
Overall size
150 caliber: outer diameter 280.0X inner diameter 150.0X high 40.0mm
Overload pressure
>2 times
Power consumption
Standby power consumption
Pressure Sensor Accuracy
0.5%FS
Protection Level
IP68
Radiation resistance (RS)
Full frequency band 2V/M and conducted full frequency band (CS) 3Vr.ms, no impact on accuracy
Service Life
≥ 5 years
Stability
± 0.5%FS/year
Structural materials
Nylon and glass fiber
Temperature measurement range
-25.0℃~ +85.0℃, error: ± 2℃
Temperature range
-25℃ ~ +85℃
Voltage Range
Vcc = 3.2± 0.4 VDC, using 3.6V lithium battery pack>12000mAH
Wake-up method
Timing\Alarm\Vibration\Tilt
Water pressure measurement range
0 ~ 1.6MPa
Applications and use cases
Architectures in which QTC403-L can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productChntek
QTC403-L
NB-IoT IP68 intelligent fire hydrant monitoring device
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details