Single-phase DC energy meter on DIN rail, designed to measure voltage, current, power and energy in a DC system up to 1000V DC with RS485 communication.
Input voltage range5-1000V DC
Interface Standard and ProtocolRS485 and MODBUS RTU
Input-Voltage — Power consumption≤0.5VA
Input-Current — Power consumption≤0.1VA
Input-Current — Shunt75mV in default, 45/60mV optional
Measurement Accuracy — Current0.2% of range maximum
Product overview
Eastron DCM230. The Eastron DCM230 single load DIN rail DC energy meter is a multifunction single-phase meter designed for DC energy systems, with a 5-1000V DC voltage input range.
Main characteristics. The meter measures RMS values on a DC system (1P+N) for voltage, current, power and active energy, with an accuracy of 0.2% of range maximum for voltage and current, and 0.5% for power and active energy. The current shunt is 75 mV by default, with 45 mV or 60 mV optional.
Power consumption. Consumption is 0.5 VA maximum on the voltage input and 0.1 VA maximum on the current input.
Interfaces and connectivity. A pulse output and an RS485 port are provided, the latter supporting the MODBUS RTU protocol. The communication address ranges from 1 to 247. The transmission speed ranges from 1200 bps to 19200 bps, with parity none (default), odd or even and 1 or 2 stop bits. The transmission distance is up to 1000 m.
Typical uses. With its RS485 port and Modbus RTU protocol, the meter can be connected to a PLC or a supervision system to report the measurements of a DC system.
Integration. The meter mounts on a DIN rail and occupies two modules.
Single-phase DC energy meter on DIN rail, designed to measure voltage, current, power and energy in a DC system up to 1000V DC with RS485 communication.
Input voltage range5-1000V DC
Interface Standard and ProtocolRS485 and MODBUS RTU
Input-Voltage — Power consumption≤0.5VA
Input-Current — Power consumption≤0.1VA
Input-Current — Shunt75mV in default, 45/60mV optional
2. Datasheet extract (recorded values)
Parameter
Value
Communication Address
1~247
Input-Current — Power consumption
≤0.1VA
Input-Current — Shunt
75mV in default, 45/60mV optional
Input-Voltage — Power consumption
≤0.5VA
Input voltage range
5-1000V DC
Interface Standard and Protocol
RS485 and MODBUS RTU
Measurement Accuracy — Active Energy
0.5% of range maximum
Measurement Accuracy — Current
0.2% of range maximum
Measurement Accuracy — Power
0.5% of range maximum
Measurement Accuracy — Voltage
0.2% of range maximum
Output — DCM230
Pulse Output + RS485 Modbus
Parity
None (default), Odd, Even
Stop Bits
1 or 2
Transmission Distance
1000m Maximum
Transmission Speed
1200bps~19200bps
Type of Measurement
RMS on DC energy system (1P+N)
Applications and use cases
Architectures in which 5-1000V can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
A building’s energy, comfort and occupancy data sit in separate systems. Sensors, meters and gateways feed one model of the building, room by room, to compare scenarios and steer the installations
To check
Data model and building plans available
Software platform hosting the twin
Sensor density needed for a useful model
Associated system blocks
SensorsMetersGateways
Need a complete solution?
Send a request for 5-1000V and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productEastron
5-1000V
Single load DC energy meter, DIN rail, RS485 Modbus
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.