The Eastron SDM230-NMI-2 single-phase meter measures active and reactive energy, current, voltage and power on a 1P+N network. It suits energy measurement and monitoring installations.
Input — Voltage — Operational Voltage80%~120% of Un
Input — Voltage — Rated Voltage (Un)230V
Input — Current — Max Current(Imax.)100A
Input — Current — Min Current(Imin.)0.15A
Input — Current — Rated Current (Ib/Iref)10A
Input — Current — Starting Current40mA
Product overview
Eastron SDM230-NMI-2 single-phase energy meter — multi-function single-phase meter for 1P+N networks, with two RS485 Modbus ports.
Main characteristics. The meter measures active and reactive energy, current, voltage, active, reactive and apparent power, power factor and frequency. It operates in RMS measurement on a single-phase AC system. The rated voltage is 230 V, with an operational voltage range of 80% to 120% of Un. The rated current is 10 A and the maximum current 100 A, with a starting current of 40 mA and a minimum current of 0.15 A.
Measurement accuracy. Active energy complies with Class 0.5 under IEC62053-22 and Class C under EN50470-3:2022. Reactive energy complies with Class 2 under IEC62053-23. Accuracy is ±0.5% for current and voltage, ±1% for active, reactive and apparent power, ±0.2% for frequency and 0.01 for power factor. Response time is below 100 mS.
Interfaces and communication. The SDM230-NMI-2 provides two RS485 Modbus ports for remote monitoring and setting. Communication addresses range from 1 to 247. Transmission speed is between 2400 and 38400 bps, with parity none (default), odd or even and 1 or 2 stop bits. Transmission distance reaches 1000 m maximum.
Typical uses. Bi-directional measurement makes the meter suitable for solar PV measurement solutions. With its RS485 Modbus ports, it can be connected to a PLC or a supervision system for data collection.
Integration. The meter has been approved to meet the requirements of EU Directive 2014/32/EU. It is available on quotation from Atlas Electronics.
The Eastron SDM230-NMI-2 single-phase meter measures active and reactive energy, current, voltage and power on a 1P+N network. It suits energy measurement and monitoring installations.
Input — Voltage — Operational Voltage80%~120% of Un
Input — Voltage — Rated Voltage (Un)230V
Input — Current — Max Current(Imax.)100A
Input — Current — Min Current(Imin.)0.15A
Input — Current — Rated Current (Ib/Iref)10A
2. Datasheet extract (recorded values)
Parameter
Value
Response time
<100 mS
Communication Address
1~247
Input — Current — Max Current(Imax.)
100A
Input — Current — Min Current(Imin.)
0.15A
Input — Current — Rated Current (Ib/Iref)
10A
Input — Current — Starting Current
40mA
Input — Voltage — Operational Voltage
80%~120% of Un
Input — Voltage — Rated Voltage (Un)
230V
Measurement Accuracy — Active Energy
Class 0.5 IEC62053-22; Class C EN50470-3:2022
Measurement Accuracy — Active Power
±1%
Measurement Accuracy — Apparent Power
±1%
Measurement Accuracy — Current
±0.5%
Measurement Accuracy — Frequency
±0.2%
Measurement Accuracy — Power
1% of range maximum
Measurement Accuracy — Power Factor
0.01
Measurement Accuracy — Reactive Energy
Class 2 IEC62053-23
Measurement Accuracy — Reactive Power
±1%
Measurement Accuracy — Voltage
±0.5%
Output — SDM230-NMI
2 Pulse Outputs + RS485 Modbus
Output — SDM230-NMI-2
2x RS485 Modbus
Parity
None (default), Odd, Even
Stop Bits
1 or 2
Transmission Distance
1000m Maximum
Transmission Speed
2400bps~38400bps
Type of Measurement
RMS on single phase AC system (1P+N)
Applications and use cases
Architectures in which 50MS can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
Solar panels produce most when nobody is home, and the surplus goes to the grid. A battery with its inverter stores this energy and returns it in the evening, with a meter measuring what the home draws
To check
Panel power and the inverter compatibility of the battery
Usable capacity compared with the evening and night consumption
Local grid connection rules for balcony and home systems
Associated system blocks
InvertersBatteryMetering
Need a complete solution?
Send a request for 50MS and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productEastron
50MS
Single-phase multi-function energy meter with 2 RS485 ports