The Eastron SDM120M single-phase DIN rail energy meter measures active and reactive energy, current, voltage and power on a 1P+N network, with RS485 Modbus RTU output and two pulse outputs.
Interface Standard and ProtocolRS485 and MODBUS RTU
Input — Voltage — Operational Voltage85~276V AC
Input — Voltage — Rated Voltage (Un)230V
Input — Current — Max Current(Imax.)45A
Input — Current — Min Current(Imin.)0.15A
Input — Current — Rated Current (Ib/Iref)5A
Product overview
Eastron SDM120M single-phase energy meter — The SDM120M is a single-phase multi-function energy meter on DIN rail, designed for measurement on 1P+N single-phase networks. It measures active and reactive energy, current, voltage, active, reactive and apparent power, power factor and frequency.
Main characteristics. RMS measurement on a single-phase AC system. Maximum current of 45 A in direct connection, without an external current transformer. Rated current of 5 A, starting current of 40 mA, operating voltage of 85 to 276 V AC for a rated voltage of 230 V. Accuracy class 0.5/1 per IEC62053-21 and class C/B per EN50470-3:2022 for active energy, class 2 per IEC62053-23 for reactive energy. Accuracy of ±0.5 % on current and voltage, ±0.2 % on frequency, ±1 % on powers and power factor.
Interfaces and connectivity. One RS485 port with MODBUS RTU protocol, communication addresses from 1 to 247, baud rates from 2400 to 38400 bps, parity none (default), odd or even, 1 or 2 stop bits. Maximum transmission distance of 1000 m. Two pulse outputs for remote monitoring.
Power and environment. Response time below 100 ms.
Typical uses. Energy consumption monitoring in residential, photovoltaic, electric vehicle charging, industrial and commercial environments. Integration into a supervision system via RS485 Modbus RTU to a PLC or gateway.
Integration. The meter mounts on DIN rail and connects on single-phase 1P+N. Available on quotation from Atlas Electronics.
The Eastron SDM120M single-phase DIN rail energy meter measures active and reactive energy, current, voltage and power on a 1P+N network, with RS485 Modbus RTU output and two pulse outputs.
Interface Standard and ProtocolRS485 and MODBUS RTU
Input — Voltage — Operational Voltage85~276V AC
Input — Voltage — Rated Voltage (Un)230V
Input — Current — Max Current(Imax.)45A
Input — Current — Min Current(Imin.)0.15A
2. Datasheet extract (recorded values)
Parameter
Value
Response time
<100 mS
Baud rate
2400bps~38400bps
Communication Address
1~247
Input — Current — Max Current(Imax.)
45A
Input — Current — Min Current(Imin.)
0.15A
Input — Current — Rated Current (Ib/Iref)
5A
Input — Current — Starting Current
40mA
Input — Voltage — Operational Voltage
85~276V AC
Input — Voltage — Rated Voltage (Un)
230V
Interface Standard and Protocol
RS485 and MODBUS RTU
Measurement Accuracy — Active Energy
Class 0.5/1 IEC62053-21; Class C/B EN50470-3:2022
Measurement Accuracy — Active Power
±1%
Measurement Accuracy — Apparent Power
±1%
Measurement Accuracy — Current
±0.5%
Measurement Accuracy — Frequency
±0.2%
Measurement Accuracy — Power Factor
±1%
Measurement Accuracy — Reactive Energy
Class 2 IEC62053-23
Measurement Accuracy — Reactive Power
±1%
Measurement Accuracy — Voltage
±0.5%
Output — SDM120M
2 Pulse Output + RS485 Modbus
Output — SDM120MB
2 Pulse Output + M-bus EN13757
Output — SDM120P
2 Pulse Output for imp/exp. energy
Parity
None (default), Odd, Even
Stop Bits
1 or 2
Transmission Distance
1000m Maximum
Transmission Speed
300bps~9600bps
Type of Measurement
RMS on single phase AC system (1P+N)
Applications and use cases
Architectures in which DLT645 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
A building’s energy, comfort and occupancy data sit in separate systems. Sensors, meters and gateways feed one model of the building, room by room, to compare scenarios and steer the installations
To check
Data model and building plans available
Software platform hosting the twin
Sensor density needed for a useful model
Associated system blocks
SensorsMetersGateways
Need a complete solution?
Send a request for DLT645 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productEastron
DLT645
Single-phase DIN rail energy meter, RS485 Modbus RTU, 45 A
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details