Overview. The Eletechsup R4M8A08 is a Modbus RTU over RS485 I/O module with eight MOSFET outputs and eight photoelectrically isolated inputs, supplied with its DIN35 rail box (model UM72).
Main characteristics. Each output is an independent channel, so a failed MOSFET does not affect the other channels and is replaced by swapping the component. The inputs are NPN, low-level active, and the input-output relationship can be set by command to associated (default) or non-associated. The outputs accept open, close, momentary, self-locking, interlock and delay commands, the delay going up to 255 seconds. Load current is 2 A for 3.5 to 5 V, 4 A for 5 to 9 V and 5 A for 9 to 30 V. The module works from 6 to 25 V DC with a current draw of 8 to 10 mA at 12 V.
Interfaces and connectivity. The Modbus RTU protocol supports function codes 03, 06 and 16 over RS485. The default baud rate is 9600 bps and can be selected with jumpers among 2400, 4800, 9600 and 19200 bps. In Modbus mode, up to 64 devices can operate in parallel on the same bus.
Power and environment. The module is designed for a DC supply of 6 to 25 V. The outputs drive DC loads of 3.5 to 30 V. The box is made of flame-retardant VO grade material, is green, and mounts on DIN35 and C45 rails. PCB dimensions are 136 x 72 x 18 mm; with the box, 140 x 88 x 40 mm. Weight is 75 g for the PCB alone and 175 g with the box.
Typical uses. The module extends PLC inputs and outputs and switches loads such as power relays, LED lighting, fans, motors or cameras, and handles forward and reverse motor control, automatic curtain control and LED lighting systems. It is also used in home automation and security monitoring.
Integration. It is controlled from a serial terminal, the Modbus Poll software, or a PLC or microcontroller. Compared with a relay board it offers low working current, silent state switching and light weight. Its limits are a load current within 5 A and control limited to DC loads of 3.5 to 30 V. The output indicator is only active when load power is present.