HM-920 – Addressable Fire Alarm Control Panel 2 Loops

Addressable Fire Alarm Control Panel 2 Loops

Alarm Panels

  • RS-485
  • RS-232
Manufacturer part number
HM-920
Manufacturer
Heiman

The Heiman HM-920 fire alarm control panel drives two wired addressable loops and up to 16 zones, with sounder and relay outputs and LAN, RS232, CAN and RS485 communication. EN54-2 and EN54-4 compliant.

Product overview

Overview. The Heiman HM-920 is an EN54-2 and EN54-4 compliant fire alarm control panel. It supervises and controls a fire detection system with two addressable wired loops using two-wire cabling, with a capacity of 16 zones.

Main characteristics. The panel provides 4 access levels, a control keypad with Mute, Silence/Resound, Lamp Test, Disable, Reset, Evacuate and navigation keys, and a 3.5-inch display. Response time is under 10 seconds.

Interfaces and connectivity. Communication interfaces include LAN, RS232, CAN and RS485, with 4G and 868 MHz available as options. Communication distance reaches 2000 m per loop wired and 2000 m wireless.

Power and environment. Mains supply is 110 V to 250 V AC, with two 12 V sealed lead-acid backup batteries. The auxiliary output delivers 24 V DC at 500 mA. The UL94 V0 rated ABS+PC enclosure has an IP30 protection index and measures 300 × 210 × 95 mm.

Typical uses. The 2 sounder outputs of 24 V DC at 500 mA and the 3 relay outputs rated 1 A at 30 V DC can drive alarm signalling, evacuation control equipment and fault signalling.

Integration. The RS485 and CAN interfaces allow networking with other panels and connection to supervision systems. The 20 mm cable entries ease wiring.