HM-921 – 4-loop addressable fire alarm control panel EN54-2 EN54-4

4-loop addressable fire alarm control panel EN54-2 EN54-4

Alarm Panels

  • RS-485
Manufacturer part number
HM-921
Manufacturer
Heiman

Heiman HM-921 fire alarm control panel compliant with EN54-2 and EN54-4, supporting up to 4 addressable 2-wire loops and 32 zones, with sounder, relay and LAN, RS485 and CAN communication outputs.

Product overview

Overview. The Heiman HM-921 is a fire alarm control panel compliant with EN54-2 and EN54-4, designed for hybrid fire detection installations combining wired and wireless devices. It manages 4 loops and 32 zones.

Main characteristics. The panel offers a capacity of 4 loops and 32 zones, a response time of less than 10 seconds and access level 4. Its fire-resistant, corrosion-resistant steel enclosure measures 300×400×110 mm, with an IP30 protection rating and 20 mm cable entries.

Interfaces and connectivity. The loops use addressable 2-wire wiring. The panel provides LAN, RS232, CAN and RS485 interfaces for linking several panels and for remote monitoring, plus optional 4G and 868 MHz. Communication distance reaches 2000 m per loop wired and 2000 m wireless.

Power and outputs. The panel is powered from AC 110V-250V and fitted with two 12V sealed lead-acid backup batteries. It provides 4 sounder outputs at DC 24V / 500mA, 4 relay outputs rated 1A at 30V DC (fire alarm signal, fault alarm, control equipment) and one auxiliary DC 24V 500mA output.

Use and integration. The sounder and relay outputs allow control of sounders, strobes, HVAC shutdown, door control and evacuation systems. The communication interfaces ease integration with a BMS or third-party monitoring platforms.

See also