The Hexing HXS100 round single-phase meter measures energy on a residential circuit rated 120 V or 240 V, with an LCD display and an IEC62056-21 optical port.
Temperature — Operating Temperature-25℃~55℃
Operating Voltage Range80%-120%Un
Storage & Transport Temp. Range-40℃~70℃
Communication Interfaces — Optical PortIEC62056-21 Security Authentication
Current — Base Current (TA)30A,15A
Current Circuit≤ 0.1 W
Product overview
Overview. The Hexing HXS100, reference FM1S/FM2S, is a single-phase round energy meter designed for residential metering. Its compact design aims at a good balance between functions and cost.
Main characteristics. The meter has an accuracy class of CA0.5 and a rated voltage of 120V/240V, for an operating voltage range of 80%-120%Un. It operates at 50Hz or 60Hz, with base currents of 15A and 30A and maximum currents of 100A and 200A. The starting current complies with ANSI-C12.20.
Interfaces and connectivity. The optical port complies with IEC62056-21 with security authentication, with a range below 6m. The LCD display has a character size of 15mm x 6.5mm.
Power and environment. The voltage circuit consumes 1.5 W or less (active) and 10 VA or less (apparent), and the current circuit 0.1 W or less. The meter has an IP54 rating, tolerates humidity up to 95% relative humidity non-condensing and operates from -25℃ to 55℃. Storage and transport range is -40℃ to 70℃.
Immunity and withstand tests. The product is tested at 4kV dielectric strength (AC voltage) for 1 minute, 4kV electrical fast transient/burst, 6kV surge immunity and 1.2/50µs impulse voltage at 6kV, as well as 8kV contact discharge and 15kV air discharge electrostatic discharge.
Dimensions and enclosure. The meter measures 177mm x 177mm x 105mm and weighs approximately 0.69 kg. The base is black PC, the inner cover cool gray or white and the outer cover transparent PC.
The Hexing HXS100 round single-phase meter measures energy on a residential circuit rated 120 V or 240 V, with an LCD display and an IEC62056-21 optical port.
Temperature — Operating Temperature-25℃~55℃
Operating Voltage Range80%-120%Un
Storage & Transport Temp. Range-40℃~70℃
Communication Interfaces — Optical PortIEC62056-21 Security Authentication
Current — Base Current (TA)30A,15A
2. Datasheet extract (recorded values)
Parameter
Value
Dimensions
177mm x 177mm x 105mm
Accuracy
CA0.5
Base
Black PC
Communication Interfaces — Optical Port
IEC62056-21 Security Authentication
Cover
Inner Cover: Cool Gray or White; Outer Cover: Transparent PC
Current — Base Current (TA)
30A,15A
Current Circuit
≤ 0.1 W
Dielectric Strength — AC Voltage Test
4kV for 1 min
Electrical Fast Transient/Burst Test
4kV
Electrostatic Discharge (Air Discharge)
15kV
EMC — Electrostatic Discharge (Contact Discharge)
8kV
Enclosure — IP Rating
IP54
Frequency
50Hz, 60Hz
Humidity
Up to 95% Relative Humidity (Non-condensing)
Impulse Voltage Test
1.2/50µs 6kV
IRDA
IEC62056-21 Security Authentication <6m
LCD Display — Character Size
15mm x 6.5mm
Maximum Current
200A, 100A
Operating Voltage Range
80%-120%Un
Packaging:
Approx. 0.1kg
Power Consumption — Voltage Circuit (Active)
≤1.5 W
Starting Current
ANSI-C12.20
Storage & Transport Temp. Range
-40℃~70℃
Surge Immunity Test
6kV
Temperature — Operating Temperature
-25℃~55℃
Terminal Cover
Cool Gray PC
Voltage Circuit (Apparent)
≤10 VA
Voltage — Rated Voltage
120V/240V
Weight — Net Weight
Approx. 0.69 kg
Integration
Points to check before using HXS100 in a design. They are derived from the recorded characteristics, not from the manufacturer's application circuits.
1Thermalrated operating range -25℃~55℃ — check it against the installation environment.
Power and communication
Current — Base Current (TA)
30A,15A
Current Circuit
≤ 0.1 W
Dielectric Strength — AC Voltage Test
4kV for 1 min
Impulse Voltage Test
1.2/50µs 6kV
Maximum Current
200A, 100A
Operating Voltage Range
80%-120%Un
Power Consumption — Voltage Circuit (Active)
≤1.5 W
Starting Current
ANSI-C12.20
Voltage Circuit (Apparent)
≤10 VA
Voltage — Rated Voltage
120V/240V
Check the exact pin assignment and the application circuit in the datasheet, or ask our experts.
Implementation checklist
Thermal : rated operating range -25℃~55℃ — check it against the installation environment.
Applications and use cases
Architectures in which HXS100 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
Solar panels produce most when nobody is home, and the surplus goes to the grid. A battery with its inverter stores this energy and returns it in the evening, with a meter measuring what the home draws
To check
Panel power and the inverter compatibility of the battery
Usable capacity compared with the evening and night consumption
Local grid connection rules for balcony and home systems
Associated system blocks
InvertersBatteryMetering
Need a complete solution?
Send a request for HXS100 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details