Product overview
Holykell HTS102. integrated insert-type temperature sensor with transmitter function, fitted with a PT100 or Pt1000 probe and an analog output of 4-20 mA, 0-5 V or 0-10 V.
Main characteristics. Probe diameter Φ6 or Φ8 optional, length 50 mm or customized, housing and process in 304 stainless steel, working pressure 40 bar standard and 300 bar customized. Response time 2.3 s for T=50 and 5.4 s for T=90. Linearity ±0.1%F.S., ±0.25%F.S. or ±0.5%F.S. optional, long-term stability 0.1%F.S.
Power and environment. Power supply 18 to 30 Vdc, with reverse polarity protection and overload voltage protection as standard, surge protection on request. Operating temperature -40 to 85 °C, storage -40 to 125 °C, protection rating IP65.
Connection. 2-wire or 3-wire wiring, insert installation.
Typical uses. Pipeline and ventilation systems, hydraulic and pneumatic systems, cooling, heating and air conditioning (HVAC) circuits, petrochemical industry.
Integration. Analog output compatible with standard 4-20 mA, 0-5 V or 0-10 V control and acquisition inputs.