Honeywell single-channel DIN rail controller for monitoring and controlling mA or mV gas detectors, with built-in action relays.
Operating Pressure Range90 to 110 kPa
Humidity range10 to 90% RH (Non-Condensing) percent
Weight range225 gram
Storage Temperature-25 to +60°C
MountingDIN Rail (TS35 - ‘Top Hat’)
AlarmRed
Product overview
Honeywell Automation Unipoint Controller (UNIPOINT-CONTROLLER) — single-channel gas detection controller mounted on a TS35 DIN rail, designed for basic monitoring and control of any mA or mV gas detector.
Main functions. The controller provides three alarm relays and one system fault relay, with alarm on and off delay from 0 to 900 seconds, latching or non-latching operation and energised or de-energised configuration. It includes built-in 63 decibel audiovisual alarms, an ultra-clear backlit display showing the units of measure, the digital gas reading and event codes, and red (alarm), amber (fault) and green (power) indicators. Configuration menus can be password protected.
Inputs and connections. Plug-in screw terminals are removable, and the controller mounts on a DIN rail through a socket that also passes power to adjacent units. Units clip together to form small to medium monitoring systems.
Power and environment. Supply voltage of 18 to 32 V DC, power consumption of 3.0 W excluding power to a 3-wire detector and 4.8 W including power to the detector. Ingress protection IP3x (indoor), storage temperature from -25 to +60 °C, operating pressure range from 90 to 110 kPa and humidity range from 10 to 90 % RH non-condensing.
Typical uses. Small and medium integrated systems, custom control cabinets and panels, unmanned equipment rooms, boiler houses, HVAC systems, analyser houses and car parks.
Honeywell single-channel DIN rail controller for monitoring and controlling mA or mV gas detectors, with built-in action relays.
Operating Pressure Range90 to 110 kPa
Humidity range10 to 90% RH (Non-Condensing) percent
Weight range225 gram
Storage Temperature-25 to +60°C
MountingDIN Rail (TS35 - ‘Top Hat’)
2. Datasheet extract (recorded values)
Parameter
Value
Humidity range
10 to 90% RH (Non-Condensing) percent
Alarm
Red
Alarm Included
Yes
Alarm Type
Built-in Audio Visual Alarms
Common Alarm Relay
(3) Alarm Relays, (1) System Fault Relay
Decibels
63 decibel
Display Included
Yes
Display Readout
Units of Measure, Digital Gas Reading and Event Code
Display Type
Ultra-Clear Backlit Display
Fault
Amber
For use with
Gas Detectors
Industry
Energy
Ingress Protection
IP3x (Indoor)
Mounting
DIN Rail (TS35 - ‘Top Hat’)
Number of Relay Outputs
4
Operating Pressure Range
90 to 110 kPa
Plug Type
Plug-in Screw Terminals
Power
Green
Power Requirement
3.0W (Excluding Power to 3-Wire Detector)|4.8W (Including Power to Detector)
Relay Included
Yes
Relay Output Configuration
Latching/Non-latching Energised/De-Energised Alarm Trip Point Rising/Falling Alarm ON/OFF Delay (0 to 900 sec)
Relay Rated Load
SPCO/3A, 240V AC/28V DC (Non-Inductive Load)
Relay Wire Size
1.5 sq mm
Security
Configuration Menus can be Password Protected to Prevent Unauthorised Access
Series Name
Unipoint DIN Controller
Software License
Software Version 5V0
Storage Temperature
-25 to +60°C
Sub-Category
Gas Detection Controllers
Visual Indicators
Alarm: Red|Fault: Amber|Power: Green
Voltage ripple
18 to 32V DC
Weight range
225 gram
X
BRV900~51400955-100
Applications and use cases
Architectures in which UNIPOINT-CONTROLLER can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Offices and classrooms get stuffy without anyone measuring why. Indoor air quality monitoring places CO2, VOC and particle sensors in the rooms and reports their values through a gateway, so ventilation can be adjusted to real occupancy
To check
Parameters to measure (CO2 alone or CO2, VOC and particles)
Battery-powered sensors or mains-powered sensors with display
Integration with the ventilation control or building management system
Associated system blocks
Air sensorsGateway
Need a complete solution?
Send a request for UNIPOINT-CONTROLLER and the other parts of your project.
Answers to the questions that the recorded characteristics of UNIPOINT-CONTROLLER can answer. A question is not asked when nothing is recorded to answer it.
1Does it support CAN bus?
Yes — recorded under "Security": Configuration Menus can be Password Protected to Prevent Unauthorised Access.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productHoneywell Automation
UNIPOINT-CONTROLLER
Single-channel DIN rail controller for mA or mV gas detector
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details