Hytronik HBIR28/2CH is a Bluetooth PIR occupancy sensor for ceiling mounting, of stand-alone type, equipped with two independent relay outputs. It is an occupancy sensor for lighting control in standard indoor spaces.
Detection. Passive infrared (PIR) detection over 360°, with a stated detection range of 9x6 and a maximum mounting height of 6.0 m. The lens is of the Standard Low-bay type and sensitivity is adjustable at 10%, 30%, 50%, 75% and 100%. Warm-up time is 20 s.
Connectivity. Bluetooth 2.4 GHz to 2.483 GHz module based on the Nordic nRF52832, with a phone-to-device range of 10 to 30 m and a transmit power of 4 dBm. Commissioning is done by app or web interface over Bluetooth, on the Koolmesh system.
Outputs and functions. Two relay outputs for on/off or volt-free contact (VFC) control, with daylight harvest function. NC relay configuration supports fail-safe lighting. The sensor has no Tri-level or Human Centric Lighting function.
Power and environment. Operating voltage 220 to 240 VAC, 50/60 Hz. Maximum capacitive load 400 VA and maximum in-rush current 80 A at 160 µs. Operating ambient temperature -20 °C to 50 °C, humidity 10% to 90%. IP20 rating, IP54 for the front part. Dimensions 78.0 x 78.0 x 79.2 mm, weight 85.0 g, mounting hole 66.0 mm.
Integration. Compatible with Hytronik accessories, including the Bluetooth mesh gateway HBGW02 and the BACnet gateway HBGW03/R, as well as the HA03 and HA09 surface mount boxes. The product status is active, make to stock.
Dual relay outputs for load control and system integration
Human Centric Lightning (HCL):
No
Humidity max:
90 %
Humidity min:
10 %
Installation Type
Stand-alone
IP Rate
IP20
IP Rate (facial part):
IP54
Lens type
Standard Low-bay
Load capacitive:
400.0000 VA
Max withstandable in-rush current:
80A@160μs
Maximum Mounting Height:
6.0000 m
Mounting height
Low-bay
Mounting Hole
66.0000 mm
Operating Voltage Range
220-240 VAC 50/60 Hz
Product Height
79.2000 mm
Product Length
78.0000 mm
Product Status:
Active / Make to Stock
Product Weight
85.0000 g
Product Width
78.0000 mm
Reliable
Fail-safe lighting support through NC relay configuration
Sensitivity
10%/ 30% /50% /75%/ 100%
Storage temperature max.:
70 °C
Storage temperature min.:
-40 °C
Tri-level (Corridor function):
No
Voltage Type:
AC
Warming-up:
20 s
Wireless
App-based setup for fast commissioning
Zhaga:
No
Applications and use cases
Architectures in which HBIR28/2CH can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Meeting rooms are booked but empty, and some areas are always full. Presence sensors, radars and counting cameras measure how spaces are really used, room by room or at entrances
To check
Presence per room or counting at entrances, or both
Privacy requirements, which favour radar or anonymous counting
Hotel rooms keep heating, cooling and lights on while empty. A room control system links thermostats, switches, door contacts and lighting controllers so the room adapts to the guest’s presence
To check
Wired bus or wireless system, depending on renovation or new build
Link with the property management system for check-in and check-out
Behaviour when the guest is absent (setback temperature, lights off)
Associated system blocks
Climate controlSwitches and panelsPresence detectionLighting control
A building’s energy, comfort and occupancy data sit in separate systems. Sensors, meters and gateways feed one model of the building, room by room, to compare scenarios and steer the installations
To check
Data model and building plans available
Software platform hosting the twin
Sensor density needed for a useful model
Associated system blocks
SensorsMetersGateways
Need a complete solution?
Send a request for HBIR28/2CH and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productHytronik
HBIR28/2CH
Bluetooth PIR occupancy sensor with two relay outputs
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details