Product overview
Overview. The ICP DAS CL-222-E is a data logger module for air quality, measuring PM1, PM2.5, PM10, CO2, temperature, humidity and dew point. It is designed for ceiling or wall mounting.
Main characteristics. The CO2 sensor is a non-dispersive infrared (NDIR) type. Particles are measured across six sizes, from 0.3 µm to 10 µm. The real-time clock logs up to 450,000 records with date and time stamps. A Form A relay output (SPST, 30 VDC at 16 A or 250 VAC at 16 A) can drive an alarm or an indoor air quality control device.
Interfaces and connectivity. The module provides one RS-485 port and one Ethernet port. It supports the DCON and Modbus RTU protocols over RS-485, and Modbus TCP and MQTT over Ethernet. Configuration is done through a web-based interface.
Power and environment. It is powered either over PoE, with a maximum consumption of 2.5 W, or from a terminal block at +12 to +48 VDC, with a maximum consumption of 2.3 W. The operating range is 0 to 50 °C, for a humidity of 10 to 90 % RH non-condensing, with an IP20 ingress protection rating. An external wall box, EWB-C150, is available for the CL-200 series.
Typical uses. The RS-485 connection with Modbus RTU allows integration with programmable logic controllers or supervision systems, for monitoring air quality in indoor premises.