Product overview
Overview. The CL-225-E is an ICP DAS air quality data logger module measuring PM1/PM2.5/PM10, NH3, temperature, relative humidity and dew point. It belongs to the CL-220-E series.
Main characteristics. The module records up to 450,000 date and time stamped records using a built-in real-time clock. It measures particles in the sizes 0.3μm, 0.5μm, 1μm, 2.5μm, 5μm and 10μm. A web-based configuration interface is included, together with a software utility, an iOS app and an Android app.
Interfaces and connectivity. The module provides one RS-485 port and one Ethernet port. It supports DCON, Modbus RTU (RS-485), Modbus TCP and MQTT (Ethernet) protocols. A relay output can trigger an alarm or control an indoor air quality (IAQ) device.
Power and environment. Power is supplied from a terminal block at +12 to +48 VDC, or via PoE. Consumption is 2.3 W maximum without PoE and 2.5 W maximum with PoE. Operating temperature is 0 to 50°C, humidity 10 to 90% RH non-condensing, ingress protection IP20. Dimensions are Ø 150 x 53 mm. Mounting is on the ceiling or the wall.
Typical uses. The module suits indoor air quality monitoring in buildings and environmental data logging connected to a controller through Modbus RTU or Modbus TCP.
Accessories. The EWB-C150 external wall box and the FLT-C002 replaceable filter patch are available as options.