Product overview
ICP DAS CL-227-E. Data logger module for indoor air quality, measuring PM1/PM2.5/PM10 particulates, HCHO formaldehyde, temperature, relative humidity and dew point.
Measurements. The module measures PM1, PM2.5, PM10 and particle counts at 0.3μm, 0.5μm, 1μm, 2.5μm, 5μm and 10μm, together with HCHO, temperature, humidity and dew point. It includes a real-time clock and stores up to 450,000 time-stamped records.
Connectivity. The CL-227-E provides one RS-485 port and one Ethernet port. It supports DCON and Modbus/RTU over RS-485, and Modbus TCP and MQTT over Ethernet. It is powered by Ethernet PoE or from a terminal block at +12 to +48 VDC, with consumption of 2.3 W maximum without PoE and 2.5 W maximum with PoE.
Configuration. A web-based configuration interface is included, along with a software utility, an iOS app and an Android app.
Environment and installation. Operating temperature 0 to 50°C, storage temperature -30 to +75°C, humidity 10 to 90% RH non-condensing, IP20 ingress protection. Ceiling or wall mounting, with the EWB-C150 external wall box available for the CL-200 series. Dimensions Ø 150 × 53 mm.
Typical uses. Indoor air quality monitoring and environmental data logging in installations connected to a PLC or supervisory system via RS-485 or Ethernet.