Product overview
Overview. The ICP DAS CL-229-E is a data logger module of the CL-200 series that measures PM1, PM2.5 and PM10 particles, CO, CO2, HCHO, total volatile organic compounds (TVOC), temperature, humidity and dew point. It is intended for indoor air quality monitoring.
Main characteristics. The CO2 sensor is a non-dispersive infrared (NDIR) type. The module stores up to 450,000 time-stamped records, using its built-in real-time clock. Particles are measured in sizes of 0.3 μm, 0.5 μm, 1 μm, 2.5 μm, 5 μm and 10 μm. A Form A relay output (SPST, 30 VDC at 16 A or 250 VAC at 16 A) can trigger an alarm or control air treatment equipment.
Interfaces and connectivity. The module provides one RS-485 port and one Ethernet port, with PoE power. Supported protocols are DCON and Modbus RTU on RS-485, and Modbus TCP and MQTT on Ethernet. A web-based configuration interface is included.
Power and environment. The module can be powered by PoE (2.5 W max.) or from a terminal block at +12 to +48 VDC (2.3 W max. without PoE). It operates between 0 and 50 °C, at 10 to 90 % RH non-condensing, with an IP20 ingress protection rating. Its dimensions are Ø 150 x 53 mm.
Installation. The module mounts on a ceiling or a wall. The EWB-C150 external wall box and the FLT-C002 replaceable filter are available as accessories.
Typical uses. The RS-485 connection with Modbus RTU allows integration into an existing PLC or supervision system, while Modbus TCP and MQTT facilitate data transfer over an Ethernet network.