Product overview
Overview. The ICP DAS EC2-P32 is an EtherCAT slave I/O module with 32 isolated digital inputs, a remote I/O module for DIN rail. It is installed by daisy chain connection, which provides a more scalable system with fewer wires.
Inputs. The module provides 32 digital input channels of wet type (sink and source) or dry type (source), powered at +24 VDC, with 3750 VDC isolation. The ON voltage level for wet contacts is +10 V to +24 V, and the OFF voltage level is +4 V maximum. LED indicators show the status of each input.
Connectivity. The module has 2 RJ45 ports for the EtherCAT bus, with on-the-fly processing, a cycle time of 100 us and distributed clocks. The maximum distance between stations is 100 m (100 Base-Tx) using shielded Ethernet/EtherCAT cable of at least CAT5. Up to 256 node IDs are supported.
Power and environment. Consumption is 3 W. The metal casing with IP40 measures 83 x 122 x 65 mm (W x L x D) and mounts on DIN rail or wall. The operating temperature range is -25 to +75 °C, storage is -30 to +80 °C, and humidity is 10 to 90% RH, non-condensing.
EMC compliance. The module is tested for electrostatic discharge (±4 kV contact, IEC 61000-4-2), fast transients (EFT, IEC 61000-4-4, 1 kV Class B) and surge (IEC 61000-4-5, ±1 kV Class A).
Integration. The module suits the collection of digital signals on an EtherCAT controller or master, with status readable from process data or directly on the LEDs.