RFU-IO – RF 433/920 MHz wireless remote I/O unit, Modbus RTU, DIN-rail

RF 433/920 MHz wireless remote I/O unit, Modbus RTU, DIN-rail

Modular DIN-Rail Remote I/O Modules

  • 3S001-1
  • O
Manufacturer part number
GUIDE+REMOTE__I_O__MODULE__AND__UNIT+WIRELESS__I_O__MODULES+RF
Manufacturer
ICP DAS

DIN-rail RF wireless remote I/O unit communicating over Modbus RTU on 433 or 920 MHz, hosting one XV series I/O board to control remote sensors and actuators.

Product overview

Overview. The ICP DAS RFU-IO is a Modbus RTU RF wireless I/O unit for DIN-rail mounting. It hosts one XV series I/O board and lets a remote Modbus master control those I/O over a radio link, through a wireless converter that turns Modbus commands into RF signals.

Wireless connectivity. The RFU-IO operates on 433 MHz or 920 MHz RF bands depending on the model (RFU-IO-433 or RFU-IO-920). It supports several user-adjustable communication rates, multi-channel configuration over a selectable frequency range, and an RSSI function for monitoring link quality. Maximum transmission range in open areas is 300 m for the RFU-IO-433, at 9600 bps and 10 dBm output power. The antenna connection is by cable, with an ANT-Base-02 base (reference 3S001-1).

I/O and expansion boards. The RFU-IO accepts XV boards providing analog voltage and current inputs and outputs, digital inputs and outputs, thermocouple or RTD inputs, or relays depending on the model. For example, the XV107 combines 8 DI with 8 NPN DO, the XV303 combines 4 AO, 4 DI and 4 relays, and the XV310 combines 4 AI, 2 AO, 4 DI and 4 PNP DO. Pair-connection mode allows point-to-point or one-to-many I/O transmission on selected models.

Deployment. A repeater mode (1 hop) addresses range limits and radio blind spots. Configuration uses rotary and DIP switches, which simplifies maintenance and device replacement. Group ID and channel selection avoid interference between networks. The ±4 kV electrostatic protection and the -25 °C to +75 °C operating range suit industrial environments.

See all specifications

Highlights

  • Model — Frequency — Transmission Distance (LoS) — Protocol — Antenna Base: Cable
  • Model — Specification — Normal Mode: Pair-connection
  • RFU-IO-433 — 433 MHz — 300 m — Modbus — ANT-Base-02: 3S001-1
  • RFU-IO-920 — 920 MHz — 500 m — Modbus — ANT-Base-02: 3S001-1
  • XV107 — 8x DI (Wet), 8x DO (NPN): O
  • XV107A — 8x DI (Wet), 8x DO (PNP): O

Typical applications

Derived from the part category, not a compatibility statement.

Technical questions

Ask a question

No published question about this part yet. Questions are reviewed before publication.

Request a quote