iSN-713-MRTU – Three-axis MEMS vibration sensor module RS-485

Three-axis MEMS vibration sensor module RS-485

Condition Monitoring Sensors

  • -25 °C ~ +75 °C
  • ±8g
  • 6 Hz to 1K Hz
  • +10 ~ +30 VDC
Manufacturer part number
ISN-713
Manufacturer
ICP DAS
Operating Temperature
-25 °C ~ +75 °C
Amplitude Range
±8g

Three-axis vibration detection module with a built-in MEMS accelerometer, designed for equipment vibration monitoring with an RS-485 Modbus RTU slave output.

Product overview

ICP DAS iSN-713-MRTU. three-axis vibration sensor module (RS-485) for equipment condition monitoring. The ICP DAS iSN-713-MRTU is a three-axis vibration detection device with a built-in MEMS accelerometer, suitable for low frequency vibration measurement.

Main characteristics. 3-axis MEMS sensor, amplitude range ±8g, frequency range 6 Hz to 1 kHz. The module provides acceleration (RMS, maximum, P-P), velocity (RMS), displacement (P-P), crest factor and the top 20 spectrum values (magnitude/frequency). A vibration eigenvalue threshold alarm function is included.

Interfaces and connectivity. One RS-485 interface (D+, D-) with Modbus RTU slave protocol. Baud rates of 9600, 19200, 38400, 57600 and 115200 bps. Data is read by transmitting Modbus RTU commands over the RS-485 interface.

Power and environment. Input range +10 to +30 VDC, consumption 0.35 W at 24 VDC. Operating temperature -25 °C to +75 °C, storage -30 °C to +80 °C, humidity 10 to 95% RH non-condensing. Dimensions 51 x 30 x 19 mm (W x L x H as published).

Typical uses and integration. Wall-mount or magnet adsorption installation. The RS-485 Modbus RTU connection allows integration with a PLC or supervisory system for real-time vibration monitoring.

See all specifications

Highlights

  • Amplitude Range: ±8g
  • Baud rate: 9600, 19200, 38400, 57600, 115200 bps
  • Consumption: 0.35 W@24VDC
  • Dimensions (mm): 51 x 30 x 19 (W x L x H)
  • Frequency Range: 6 Hz to 1K Hz
  • Humidity: 10 ~ 95% RH, Non-condensing

Typical applications

Derived from the part category, not a compatibility statement.

Good to know before integrating

  • Thermal: rated operating range -25 °C ~ +75 °C — check it against the installation environment.