M-2018-16 – 16-channel Thermocouple Input Module, Modbus RTU and DCON

16-channel Thermocouple Input Module, Modbus RTU and DCON

Modular DIN-Rail Remote I/O Modules

  • RS-485
  • Modbus
Manufacturer part number
M-2018
Manufacturer
ICP DAS

The M-2018-16 is a 16-channel differential analog input module for DIN-rail mounting, designed to measure thermocouples, voltages and currents, with RS-485 communication using Modbus RTU or DCON.

Product overview

Overview. The ICP DAS M-2018-16 is a 16-channel differential thermocouple input module from the M-2000 RS-485 remote I/O range, designed for DIN-rail installation. It supports the Modbus RTU and DCON protocols.

Analog inputs. The module accepts voltage inputs from ±15 mV to ±2.5 V, current inputs of 4–20 mA, 0–20 mA or ±20 mA, and thermocouple inputs of types J, K, T, E, R, S, B, N, C, L, M and L DIN43710. Each thermocouple channel features open-wire detection. The cold junction compensation (CJC) offset is adjustable.

Protection. The module provides overvoltage protection up to ±120 VDC, EMS protection (EFT, ESD, surge) and 3000 VDC intra-module isolation. Reverse polarity protection is included. It has a dual watchdog timer (module and communication, programmable).

Communication and power. The module has one RS-485 port, baud rates from 1200 to 115200 bps and data formats (N, 8, 1), (N, 8, 2), (E, 8, 1) and (O, 8, 1). The 10 kΩ bias resistor is selectable by DIP switch. The input range is +10 to +48 VDC, with a consumption of 0.5 W. One status LED indicates power and communication.

Environment and installation. The operating temperature range is -25 to +75 °C and the storage range is -40 to +85 °C, with humidity of 10 to 95 % RH, non-condensing. Dimensions are 31 x 157 x 132 mm (W x L x H).

Integration. Thanks to its RS-485 port and the Modbus RTU protocol, the M-2018-16 can be connected to a PLC or SCADA system supporting this protocol, or operated with the DCON protocol.