The M-7003-G is a DIN-rail remote I/O module from ICP DAS combining 8 analog inputs with 16-bit resolution and 4 Form A relay outputs, controlled by Modbus RTU or DCON over an RS-485 port.
Operating Temperature-25 ~ +75 °C
Input Range+10 ~ +30 VDC
Consumption1.8 W
Storage Temperature-40 ~ +85 °C
Channels4
Dimensions (mm)72 x 123 x 35 (W x L x H)
Product overview
Overview. The ICP DAS M-7003-G is a DIN-rail remote I/O module combining 8 analog inputs and 4 Form A relay outputs in a single housing.
Main characteristics. Input resolution is 16 bits. Each analog channel can be configured individually, with ranges of ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V, ±20 mA, 0 ~ 20 mA and 4 ~ 20 mA. Voltage or current input is selected by jumper. The inputs provide 120 VDC high overvoltage protection and photocoupler isolation. Relay operate time is 3 ms and release time is 2 ms. The module includes a built-in dual watchdog.
Interfaces and connectivity. The module has one RS-485 port and supports Modbus RTU and DCON protocols. Baud rates range from 1200 to 115200 bps, with data formats (N, 8, 1), (N, 8, 2), (E, 8, 1) and (O, 8, 1). Safe values and power-on values are programmable.
Power and environment. The input voltage range is +10 to +30 VDC, with reverse polarity protection. Power consumption is 1.8 W. The operating temperature range is -25 to +75 °C and the storage range is -40 to +85 °C. Humidity tolerance is 10 to 95 % RH, non-condensing. Dimensions are 72 x 123 x 35 mm (W x L x H).
Typical uses. With its RS-485 port and Modbus RTU support, the module can be connected to a programmable controller or a Modbus supervisor for analog measurement acquisition and relay-based control of loads.
Integration. Rated endurance is 2 x 10^7 mechanical operations and 10^5 electrical operations for the relays.
The M-7003-G is a DIN-rail remote I/O module from ICP DAS combining 8 analog inputs with 16-bit resolution and 4 Form A relay outputs, controlled by Modbus RTU or DCON over an RS-485 port.
8-ch AI and 4-ch Relay Module using DCON and Modbus Protocols (Gray Cover) (RoHS)
Mechanical Endurance
2 x 107 ops.
Operate Time
3 ms
Operating Temperature
-25 ~ +75 °C
Ports
1 x RS-485
Power on Value
Programmable
PRODUCT SERIES
M-7003-G CR
DESCRIPTION 8-ch AI and 4-ch Relay Module using DCON and Modbus Protocols (Gray Cover) (RoHS)
Protocol
Modbus RTU, DCON
Release Time
2 ms
Reverse Polarity Protection
Yes
Safe Value
Programmable
SG-3000 series
Signal Conditioning Modules for Thermocouple, RTD, DC Voltage, DC Current and Power Input Transformers
SG-770 CR
7/14 channel Surge Protector (RoHS)
Storage Temperature
-40 ~ +85 °C
tM-7520U CR
Tiny Isolated RS-232 to RS-485 Converter (RoHS)
tM-7561 CR
Tiny USB to Isolated RS-485 Converter with CA-USB18 Cable (RoHS)
tM-SG4 CR
RS-485 Pull-high/Pull-low and Termination Resistor Module (RoHS)
Type
Power Relay (Form A)
Integration
Points to check before using M-7003-G in a design. They are derived from the recorded characteristics, not from the manufacturer's application circuits.
1Thermalrated operating range -25 ~ +75 °C — check it against the installation environment.
Power and communication
Consumption
1.8 W
Power on Value
Programmable
Check the exact pin assignment and the application circuit in the datasheet, or ask our experts.
Implementation checklist
Thermal : rated operating range -25 ~ +75 °C — check it against the installation environment.
Applications and use cases
Architectures in which M-7003-G can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
A proprietary PLC locks the project into one vendor’s tools. Industrial controllers built on the Raspberry Pi Compute Module run Linux, Node-RED, Python or CODESYS on DIN rail, with I/O modules, an operator panel and a cellular router for remote access
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productICP DAS
M-7003-G
8-channel analog input and 4-relay remote I/O module
DESCRIPTION 10-ch Universal AI Module using DCON and Modbus Protocols (Gray Cover) (RoHS); Includes DB-1820 Daughter Board and Plastic DIN Rail (4PAPP-006-G)
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details