The M-7013PD-G is a 1-channel DIN-rail RTD input module that measures temperature with Pt100, Ni120 or Pt1000 sensors, with 1 digital input, 2 digital outputs and an LED display.
Load Current700 mA/Channel
Frequency50 Hz
Channels1
Load voltage3.5 ~ 50 VDC
Max. Counts65535 (16-bit)
OFF Voltage LevelOpen
Product overview
Overview. The ICP DAS M-7013PD-G is a 1-channel RTD input module for DIN rail, from the M-7000 series with DCON and Modbus protocols. It measures temperature using Pt100, Ni120 and Pt1000 RTD sensors.
Main characteristics. The module supports 2-, 3- and 4-wire RTD connections and detects open wires. It eliminates lead resistance for 3- and 4-wire connections. One digital input provides event counting at 50 Hz, with a 16-bit counter (65535 counts maximum).
Outputs and alarms. The module has 2 digital outputs of Dry Contact type, with high and low alarms and overload protection (1.4 A). Safe and power-on values are programmable.
Power and environment. The module provides 3000 VDC intra-module isolation and a built-in dual watchdog. It is supplied with an LED display.
Connectivity and integration. The module communicates over RS-485 with DCON and Modbus protocols, allowing connection to a PLC or supervision system. It can be combined with the RS-485 repeaters, converters and termination modules of the ICP DAS range.
The M-7013PD-G is a 1-channel DIN-rail RTD input module that measures temperature with Pt100, Ni120 or Pt1000 sensors, with 1 digital input, 2 digital outputs and an LED display.
Load Current700 mA/Channel
Frequency50 Hz
Channels1
Load voltage3.5 ~ 50 VDC
Max. Counts65535 (16-bit)
2. Datasheet extract (recorded values)
Parameter
Value
Channels
1
Frequency
50 Hz
I-7013 CR
1-ch RTD Input Module using DCON Protocol (Blue Cover) (RoHS)
I-7013-G CR
1-ch RTD Input Module using DCON Protocol (Gray Cover) (RoHS)
I-7013D CR
1-ch RTD Input Module with LED Display using DCON Protocol (Blue Cover) (RoHS)
1-ch RTD Input Module with 1-ch DI and 2-ch DO using DCON and Modbus Protocols (Gray Cover) (RoHS)
M-7013PD-G CR
1-ch RTD Input Module with 1-ch DI, 2-ch DO and LED Display, using DCON and Modbus Protocols (Gray Cover) (RoHS)
Max. Counts
65535 (16-bit)
OFF Voltage Level
Open
ON Voltage Level
Close to GND
Overload Protection
1.4 A
Overvoltage Protection
±30 VDC
Power on Value
Programmable
PRODUCT SERIES
M-7013PD-G CR
DESCRIPTION 1-ch RTD Input Module with 1-ch DI, 2-ch DO, and LED Display, using DCON and Modbus Protocols (Gray Cover) (RoHS)
Safe Value
Programmable
SG-3000 series
Signal Conditioning Modules for Thermocouple, RTD, DC Voltage, DC Current and Power Input Transformers
SG-770 CR
7/14 channel Surge Protector (RoHS)
Short-circuit Protection
Yes
Sink/Source (NPN/PNP)
Source
tM-7520U CR
Tiny Isolated RS-232 to RS-485 Converter (RoHS)
tM-7561 CR
Tiny USB to Isolated RS-485 Converter with CA-USB18 Cable (RoHS)
tM-SG4 CR
RS-485 Pull-high/Pull-low and Termination Resistor Module (RoHS)
Type
Dry Contact
Applications and use cases
Architectures in which M-7013PD-G can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
A proprietary PLC locks the project into one vendor’s tools. Industrial controllers built on the Raspberry Pi Compute Module run Linux, Node-RED, Python or CODESYS on DIN rail, with I/O modules, an operator panel and a cellular router for remote access
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productICP DAS
M-7013PD-G
1-ch RTD Input Module with 1-ch DI, 2-ch DO and LED Display
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.