The MN-AD8-DIN is a Motionnet 8-channel analog input remote I/O module for DIN-rail mounting, measuring ±10 V signals on a Motionnet network.
Operating Temperature0 ~ +60 °C
Input Range24VDC +/-5% (1000 V isolated)
Range+/- 10 V
Consumption3 W Max.
Storage Temperature-20 ~ +80°C
Channels8
Product overview
Overview. The MN-AD8-DIN from ICP DAS is a Motionnet 8-channel analog input module for DIN-rail mounting, intended for remote I/O. It measures ±10 V signals on eight channels with 16-bit resolution and a sampling rate of 250 k sps.
Main characteristics. Each channel offers a range of +/- 10 V and a resolution of 16 bits. An internal 5 V reference ensures high precision and low drift, and offset and gain calibration values are stored in EEPROM.
Interfaces and connectivity. The module provides an RJ-45 communication port and a Motionnet bus whose transfer speed is selectable at 2.5, 5, 10 or 20 Mbps by DIP switch. A termination resistor is built in, and status LEDs show the communication state (Link, Error).
Power and environment. The module operates from a 24 VDC ±5% supply, isolated at 1000 V, and consumes 3 W maximum. Its operating temperature range is 0 to +60 °C, and its humidity rating is 10 to 90% RH, non-condensing.
Integration. The module mounts on a DIN rail and joins a Motionnet network, with up to 64 modules per communication port. The communication latency between two devices is 15.1 μs.
DESCRIPTION Distributed Motionnet 8-ch Analog Input Module (RoHS)
Range
+/- 10 V
Resolution
16-bit
Sampling Rate
250 k sps
STATUS
Communication state (Link, Error) Internal 3.3 V Power Termination Resistor Switch
Storage Temperature
-20 ~ +80°C
Transfer Speed
Selectable 2.5, 5, 10 or 20 Mbps by DIP Switch
Integration
Points to check before using MN-AD8 in a design. They are derived from the recorded characteristics, not from the manufacturer's application circuits.
1Thermalrated operating range 0 ~ +60 °C — check it against the installation environment.
Power and communication
Consumption
3 W Max.
Check the exact pin assignment and the application circuit in the datasheet, or ask our experts.
Implementation checklist
Thermal : rated operating range 0 ~ +60 °C — check it against the installation environment.
Applications and use cases
Architectures in which MN-AD8 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
A proprietary PLC locks the project into one vendor’s tools. Industrial controllers built on the Raspberry Pi Compute Module run Linux, Node-RED, Python or CODESYS on DIN rail, with I/O modules, an operator panel and a cellular router for remote access
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details