SC-6104-W5 – 4-relay RS-485 fan coil controller with AC digital input

4-relay RS-485 fan coil controller with AC digital input

Fan Coil Controllers

  • -25 to +75°C
  • -40°C ~ +80°C
  • +10 ~ +30 VDC
  • RS-485
Manufacturer part number
SC-6104
Manufacturer
ICP DAS
Operating Temperature
-25 to +75°C
Operating Temperature Range
-40°C ~ +80°C

The SC-6104-W5 is a fan coil unit controller with 4 relay outputs and one isolated AC digital input, communicating over RS-485 with Modbus RTU or DCON protocols.

Product overview

ICP DAS SC-6104-W5. 3-speed fan coil unit controller for HVAC, with RS-485 communication. The SC-6104-W5 is an easy-to-use fan control module that requires no specialist skills to install and operate, and no software is needed to control the output channels.

Function. The module provides local and remote direct control of the relays ON/OFF and remote status monitoring. It has 1 isolated AC digital input (photocoupler isolation) and 4 form C relay outputs. The sink-type input, wired directly, can control the 4-channel relay ON and OFF sequence without a remote host.

Electrical characteristics. Operating voltage 250 VAC or 30 VDC, maximum load current 20 A (NO) / 16 A (NC) at 250 VAC, recommended working current 5 A. AC input: ON voltage level 85 VAC, OFF voltage level 60 VAC, voltage range 90 to 240 VAC. Operating time 20 ms maximum, release time 10 ms maximum. Isolation 5000 Vrms. Consumption 100 mA at 24 VDC (2.4 W maximum), input voltage range +10 to +30 VDC.

Communication. RS-485 interface with Modbus RTU or DCON protocol, data format N,8,1 / O,8,1 / E,8,1 / N,8,2, fixed 9600 bps in hardware configuration. Node address 128 to 159 in hardware configuration and 0 to 255 in software configuration; for Modbus RTU, address 0 becomes 1 automatically. RJ-11 connector (6P4C or 6P6C) and 4-pin screw terminal.

Indicators and protection. 4 LEDs indicate the digital outputs and 1 LED indicates power. Power-on value function available. ESD protection of ±4 kV contact and EFT protection of ±1 kV on power and communication lines. Electrical life 100,000 operations, mechanical life 10,000,000 operations.

Environment and installation. Operating temperature -25 to +75 °C, storage temperature -30 to +85 °C, humidity 10 to 90 % RH non-condensing. DIN-rail mounting. Dimensions 116 mm x 122 mm x 64 mm. RoHS compliant.

Integration. The module fits into an existing RS-485 network using Modbus RTU or DCON, alongside other ICP DAS devices such as the tM-7520U RS-232 to RS-485 converter, the tM-7561 USB to RS-485 converter and the TPD-280 touch HMI.

See all specifications

Highlights

  • Baud rate: Hardware Confi guration: Fixed 9600 bps
  • Connector: RJ-11 (6P4C or 6P6C) / 4-pin Screw Terminal
  • Consumption: 100 mA @ 24 VDC (2.4 W Max.)
  • Data format: N,8,1 / O,8,1 / E,8,1 / N,8,2
  • Digital Output: 4 LED as digital output indicator
  • Dimensions W x L x H: 116 mm x 122 mm x 64 mm

Good to know before integrating

  • Thermal: rated operating range -25 to +75°C — check it against the installation environment.
  • Thermal: rated operating range -40°C ~ +80°C — check it against the installation environment.

Technical questions

Ask a question

No published question about this part yet. Questions are reviewed before publication.