OC 0.66-130×40II – Split core current transformer class 0.5 for outdoor use

Split core current transformer class 0.5 for outdoor use

Current Transformers Sensors

  • 1500A
  • 5A
  • 50/60Hz
  • 2000A
Manufacturer part number
HIGH-ACCURACY-CURRENT-TRANSFORMER
Manufacturer
IVY Metering
Frequency
50/60Hz
Accuracy; (S1-S2)
0.5

IVY Metering split core current transformer with openable core, class 0.5, 20 VA rated burden, for current measurement outdoors on 660 V rated voltage, 50/60 Hz.

Product overview

Overview. The IVY Metering OC 0.66-130×40II is a split core current transformer with an openable core, designed for current measurement on distribution and metering networks. It has a rated voltage of 660 V and operates at 50/60 Hz.

Main characteristics. The product offers a rated primary current of 200 A, 800 A or 3000 A for a rated secondary current of 5 A, with coil ratios of 1:40, 1:160 and 1:300. Its accuracy class is 0.5 and its rated burden is 20 VA, with 2.5 VA, 10 VA and 15 VA loads in the configuration variants. The dark blue housing is flame retardant to V0 or V1 and withstands 120 °C.

Insulation and environment. The withstand voltage between primary and secondary is 3000 Vac (1 mA, 1 min) and the insulation resistance is at least 100 MΩ at 500 Vdc. The insulation class is E. The product complies with RoHS 2.0, operates between −30 °C and +120 °C and can be used at altitudes up to 3000 m.

Typical uses. This openable-core transformer clamps onto an existing conductor without interrupting the circuit, suiting current measurement in outdoor distribution cabinets and metering panels.

Available on quotation from Atlas Electronics.

See all specifications

Highlights

  • 额定输入电流; (穿芯) — 500A — 1500A — 3000A: 2000A
  • Accuracy; (S1-S2): 0.5
  • Coil Ratio; (N1:N2) — 1:40 — 1:160: 1:300
  • Environmental Standards: RoHS2.0
  • Frequency: 50/60Hz
  • Insulation Class: E