KEW 3126 – Insulation resistance tester 500 to 5000 V

Insulation resistance tester 500 to 5000 V

Insulation Resistance Testers

  • Max. 5mA
  • ±2%rdg±3dgt
  • 5000VDC; +20%; -0%
  • DC12V : LR14×8 pcs.
Manufacturer part number
KEW_3126
Manufacturer
Kyoritsu
Measuring Range
30 - 600V AC/DC (50/60Hz)
Short Circuit Current
Max. 5mA

The Kyoritsu KEW 3126 is an insulation resistance tester with 500 to 5000 V test voltages, measurements up to 1 TΩ, and polarization index (PI) and dielectric absorption ratio (DAR) functions.

Product overview

Overview. The Kyoritsu KEW 3126 is an insulation resistance tester (megohmmeter) with test voltages of 500, 1000, 2500 and 5000 V. It measures insulation up to 1 TΩ and shows results on a large digital display with bar graph indication and white LED backlight. Main characteristics — Measuring ranges from 0.0 to 99.9 MΩ, 100 to 999 MΩ and up to 1000 GΩ depending on the voltage, with an accuracy of ±2%rdg ±3dgt. It calculates the polarization index (PI) and dielectric absorption ratio (DAR), and displays the output voltage and discharge voltage. A filter function reduces noise interference for stable measurement. It includes automatic discharge, an output voltage warning, automatic power off and a battery indicator. Maximum short-circuit current of 5 mA. AC or DC voltage measurement from 30 to 600 V. Safety and power — Compliant with IEC 61010-1 CAT III 600V, pollution degree 2, IEC 61010-031 and IEC 61326. Powered by 8 LR14 (size C) alkaline batteries. Dimensions 205 × 152 × 94 mm, approximately 1.8 kg. Typical uses — Insulation testing of cables, motors, transformers and electrical installations at the test voltages listed. Accessories — Supplied with line probe 7165A, earth cord 7224A, guard cord 7225A, hook type prod 8019, hard case 9159, 8 LR14 batteries and instruction manual. Optional line probes 7168A and 7253 and recorder adaptor 8302. The manufacturer presents this product as discontinued.

See all specifications

Highlights

  • Current consumption: 1000mA approx. (During measurement)
  • Accuracy: ±2%rdg±3dgt
  • Applicable Standards: IEC 61010-1 CAT III 600V Pollution degree 2 IEC 61010-031, IEC 61326
  • Dimension: 205(L) × 152(W) × 94(D)mm
  • Measuring Range: 30 - 600V AC/DC (50/60Hz)
  • Power Source: DC12V : LR14×8 pcs.

See also

Technical questions

Ask a question

No published question about this part yet. Questions are reviewed before publication.

Request a quote