TF1100-DC – Non-invasive ultrasonic flowmeter, dual channel, transit time

Non-invasive ultrasonic flowmeter, dual channel, transit time

Ultrasonic Flow Meters

  • -10℃ to +60℃
  • 0.5s
  • Std:10m
  • Wall-mounted
Manufacturer part number
NON-INVASIVE-ULTRASONIC-FLOWMETER-FLOW-TOTALIZER
Manufacturer
Lanry
Operating Temperature
-10℃ to +60℃
Response time
0.5s

Non-invasive transit-time ultrasonic flowmeter, clamped on the outer pipe wall to measure liquid and liquefied gas flow. Intended for maintenance, control and temporary replacement of installed meters.

Product overview

Lanry TF1100-DC is a clamp-on transit-time ultrasonic flowmeter that measures the flow of liquids and liquefied gases in a fully filled pipe without cutting the pipe or interrupting the process. — Measurement principle — It uses the ultrasonic transit-time difference correlation principle. The transducers are mounted on the external surface of the pipe, for non-invasive and non-intrusive measurement.

Main characteristics. Dual-channel non-invasive transducers give an accuracy of ±0.5% of reading at flow rates above 0.3 m/s, and a repeatability of 0.15% of reading. The flow velocity range is 0.01 to 15 m/s, bi-directional. Response time is 0.5 s, the damping of the displayed value is user-selectable from 0 to 99 s, and resolution is 0.1 mm/s. Pipe diameter range is 20-50 mm for type B and 40-4000 mm for type A. Transducers are available in aluminum or stainless steel SUS304.

Interfaces and connectivity. 4~20 mA output (accuracy 0.1%), OCT pulse output, relay, RS485 with Modbus, and a data logger. A 4.3-inch color LCD with 5 lines and a 16-key keypad allow configuration. Units are user-configured in English or metric, and totals can be expressed in gallons, ft³, barrels, lbs, liters, m³ or kg. An optional thermal energy measurement in GJ or kWh uses a Pt1000 sensor from 0 to 200 °C (accuracy ±0.1%).

Power and environment. Power supply AC 85-265 V or DC 24 V / 500 mA. Fiberglass housing, wall-mounted, IP66 according to EN60529. Operating temperature -10 °C to +60 °C, minimum operating temperature -30 °C, suited liquid temperature -35 °C to 200 °C. Dimensions 244 × 196 × 114 mm, weight 2.4 kg, standard cable length 10 m. Keypad and system lockout protect the settings.

Typical uses. Maintenance and troubleshooting, replacement of defective meters, performance checks of pumps and regulating valves, flow measurement in water and wastewater, petrochemical and chemical industries, refrigeration and air conditioning systems, food, beverage and pharmaceutical industries.

Integration. The meter connects to a PLC or supervisory system through its RS485 port using Modbus, or through its 4-20 mA output.

See all specifications

Highlights

  • Response time: 0.5s
  • Cable Length: Std:10m
  • Communication: 4~20mA(accuracy 0.1%),OCT, Relay, RS485 (Modbus),data logger
  • Damping of displayed value: 0-99s(selectable by user)
  • Degree of protection: IP66 according to EN60529
  • Display: 4.3’’ color LCD 5 lines display, 16 keys

Good to know before integrating

  • Thermal: rated operating range -10℃ to +60℃ — check it against the installation environment.