Lanry DOF6000 portable flow meter measuring velocity, water depth and conductivity in rivers, streams, open channels and partially filled pipes.
Environmental — Operating Temperature0°C 〜+60°C water temperature
Operating Temperature0°C ~+60°C
Temperature range0°C to 60°C
Depth (Pressure) — Range:0mm to 10000mm (10m)
Depth (Ultrasonic) — Range:20mm to 5000mm (5m)
Tilt (Accelerometer) — Range:±70° in roll and pitch axes.
Product overview
Overview. The Lanry DOF6000 portable flow meter combines a flow calculator and the Ultraflow QSD 6537 sensor to measure water velocity, depth and conductivity in rivers, streams, open channels and partially filled pipes. The calculator can determine the cross-sectional area from up to 20 coordinate points describing the shape of the channel.
Measurement. Velocity is measured by the ultrasonic Doppler principle in quadrature sampling mode, in both flow directions, over a range of 20 mm/s to 13.2 m/s with an accuracy of ±1 % R. Water depth is measured by two principles: ultrasonic, from 20 mm to 5000 mm with an accuracy of ±1 mm, and pressure, from 0 to 10000 mm with an accuracy of ±2 mm. Electrical conductivity is measured by a four-electrode sensor, from 0 to 200,000 µS/cm, with an accuracy of ±1 % of the measurement. Barometric pressure compensation is built in.
Connectivity. An RS485 Modbus RTU output allows direct connection to a computer or PLC, with cable runs up to 500 m. Pulse, 4-20 mA (flow and depth), SDI-12 and GPRS outputs are also available, together with a 16 GB data logger.
Power and environment. The calculator is powered from 220 VAC and 12-24 VDC, the sensor from 12 VDC. The sensor has an epoxy-sealed body rated IP68 and operates between 0 °C and +60 °C. The calculator is rated IP66 and its 4.5-inch colour LCD display simplifies on-site reading.
Typical uses. Flow measurement in rivers and streams, monitoring of open channels, and leak detection on partially filled pipelines, with simultaneous recording of velocity, depth and conductivity.
Points to check before using PORTABLE-OPEN-CHANNEL-FLOW-METER-MODBUS-RTU in a design. They are derived from the recorded characteristics, not from the manufacturer's application circuits.
1Thermalrated operating range 0°C 〜+60°C water temperature — check it against the installation environment.
2Thermalrated operating range 0°C ~+60°C — check it against the installation environment.
Power and communication
Power supply
Calculator: 220VAC& 12-24VDC; Sensor:12VDC
Check the exact pin assignment and the application circuit in the datasheet, or ask our experts.
Implementation checklist
Thermal : rated operating range 0°C 〜+60°C water temperature — check it against the installation environment.
Thermal : rated operating range 0°C ~+60°C — check it against the installation environment.
Applications and use cases
Architectures in which PORTABLE-OPEN-CHANNEL-FLOW-METER-MODBUS-RTU can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
A proprietary PLC locks the project into one vendor’s tools. Industrial controllers built on the Raspberry Pi Compute Module run Linux, Node-RED, Python or CODESYS on DIN rail, with I/O modules, an operator panel and a cellular router for remote access
Answers to the questions that the recorded characteristics of PORTABLE-OPEN-CHANNEL-FLOW-METER-MODBUS-RTU can answer. A question is not asked when nothing is recorded to answer it.
1Does it support RS-485?
Yes — recorded under "Output": Pulse, 4-20mA (Flow & Depth), RS485/Modbus, Datalogger, GPRS.
2Does it support Modbus?
Yes — recorded under "Output": Pulse, 4-20mA (Flow & Depth), RS485/Modbus, Datalogger, GPRS.
3What is the operating temperature range?
0°C 〜+60°C water temperature (source: Environmental — Operating Temperature).
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productLanry
PORTABLE-OPEN-CHANNEL-FLOW-METER-MODBUS-RTU
Portable open channel flow meter with RS485 Modbus RTU output
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details