17927714-00
Non-insulated Cable RF Admittance Level Transmitter 4-20mA

- Operating Temperature
- -40~150℃
- Measuring Range
- 0~30m
- Storage Temperature
- -20 ℃ ~ + 65 ℃
- Ambient temperature
- -40 ℃ ~ + 70 ℃
Non-insulated Cable RF Admittance Level Transmitter 4-20mA
RF admittance level transmitter with a non-insulated flexible cable probe, measuring up to 30 m for insulating solids and insulating liquids.
Overview. The Nuoying NYSP-M18 RF admittance level transmitter is a radio-frequency admittance level measurement product with a non-insulated flexible cable probe, designed for continuous level measurement of insulating solids and insulating liquids.
Main characteristics. Measuring range of 0 to 30 m, adjustable delay of 0 to 30 s, power supply of 13 to 35 V DC, process connection by thread or flange (optional). The product is rated for a process pressure of -0.1 to 8.0 MPa and a process temperature of -40 to 150 °C.
Signal and communication. 4-20 mA output with HART, RS485 and Modbus protocols.
Environment and protection. Ambient temperature from -40 to +70 °C, storage temperature from -20 to +65 °C, IP67 protection class. Explosion-proof certificate, Exia II CT6 grade (selective).
Typical uses. Continuous level monitoring of insulating solids or insulating liquids in industrial plants, with signal transmission to a PLC or supervision system via RS485/Modbus or HART.
Installation. The probe must not touch the tank wall and must be kept more than 600 mm from it. It must not be installed directly in the path of a filling inlet. The cable probe must be straightened after installation to avoid short circuit with the tank wall. The instrument must be reliably grounded.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for 17927714-00, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| Ambient temperature | -40 ℃ ~ + 70 ℃ |
| Applications | Insulative solid, insulating liquid |
| Certification | Explosion-proof certificate |
| Delay | 0 ~ 30 s adjustable |
| Explosion-proof grade | ExiaⅡCT6(selective) |
| Measuring Range | 0~30m |
| Model Number | NYSP-M18 |
| Operating Temperature | -40~150℃ |
| Power supply | (13-35)vDC |
| Probe Type | Non-insulated flexible cable |
| Process Connection | Thread/Flange(selective) |
| Process pressure | -0.1~8.0MPa |
| Process Temperature | -40~150℃ |
| Protection Class | IP67 |
| Protection Grade | Display Instrument IP67, IP67 |
| Signal Output | 4...20mA/HART/RS485/Modbus... |
| Storage Temperature | -20 ℃ ~ + 65 ℃ |
No specification matches.
Last verification : 2026-11-02
Official documents and the technical data recorded for 17927714-00. For a missing document or a specific revision, our experts send it to you.
RF admittance level transmitter with a non-insulated flexible cable probe, measuring up to 30 m for insulating solids and insulating liquids.
| Parameter | Value |
|---|---|
| Ambient temperature | -40 ℃ ~ + 70 ℃ |
| Applications | Insulative solid, insulating liquid |
| Certification | Explosion-proof certificate |
| Delay | 0 ~ 30 s adjustable |
| Explosion-proof grade | ExiaⅡCT6(selective) |
| Measuring Range | 0~30m |
| Model Number | NYSP-M18 |
| Operating Temperature | -40~150℃ |
| Power supply | (13-35)vDC |
| Probe Type | Non-insulated flexible cable |
| Process Connection | Thread/Flange(selective) |
| Process pressure | -0.1~8.0MPa |
| Process Temperature | -40~150℃ |
| Protection Class | IP67 |
| Protection Grade | Display Instrument IP67, IP67 |
| Signal Output | 4...20mA/HART/RS485/Modbus... |
| Storage Temperature | -20 ℃ ~ + 65 ℃ |
Points to check before using 17927714-00 in a design. They are derived from the recorded characteristics, not from the manufacturer's application circuits.
| Power supply | (13-35)vDC |
Check the exact pin assignment and the application circuit in the datasheet, or ask our experts.
Answers to the questions that the recorded characteristics of 17927714-00 can answer. A question is not asked when nothing is recorded to answer it.
Yes — recorded under "Signal Output": 4...20mA/HART/RS485/Modbus....
Yes — recorded under "Signal Output": 4...20mA/HART/RS485/Modbus....
-40~150℃ (source: Operating Temperature).
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Non-insulated Cable RF Admittance Level Transmitter 4-20mA

Conductive Solid Liquid RF Admittance Level Transmitter 4Mpa Minus 40 To 800 Degree

Adjustable Soft Rope RF Admittance Level Sensor High Temperature Insulation

NYUHZ Plate Magnetic Level Transmitter 6m Flange Installation 220VAC 1A

Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | 17927714-00 |
| Manufacturer | Nuoying |
Level Transmitters
Submersible liquid level sensor, 0-5 m range, 0.5-4.5 V output
Price on request
Level Transmitters
60 GHz Radar Level Sensor with RS485 MODBUS RTU Output
Price on request
Level Transmitters
Deep-water level transmitter with 4-20 mA output · Ref. : MPM426WS
Price on request
Level Transmitters
Industrial LoRaWAN ultrasonic level sensor
Price on request
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details