LS200-CM3 – IP53 LoRaWAN Three-Phase Current Meter

IP53 LoRaWAN Three-Phase Current Meter

Energy Monitoring Devices

  • LoRaWAN
Manufacturer part number
3-PHASE
Manufacturer
Planet Technology

LoRaWAN sensor for real-time three-phase current monitoring in industrial power systems. IP53 enclosure with three 75A clamp-on current transformers.

Product overview

Overview. The Planet Technology LS200-CM3 LoRaWAN three-phase current meter is a three-phase current sensor designed for power monitoring in industrial electrical installations. It is available in two versions: LS200-CM3-868M for the EU868 band (863–870 MHz) and LS200-CM3-915M for the US915 band (902–928 MHz).

Main characteristics. The sensor measures currents from 100 mA to 75 A using three 75 A clamp-on current transformers (clamp-on CT). Its ingress protection rating is IP53. The enclosure measures 112 x 88.19 x 32 mm and weighs 141 g. The operating temperature range is -20 °C to 55 °C, and the storage temperature range is -40 °C to 85 °C. Relative humidity tolerance is below 90 % RH, non-condensing.

Interfaces and connectivity. The sensor operates on LoRaWAN with OTAA and ABP activation modes, in Class A. It is compatible with standard LoRaWAN gateways, including the Planet Technology LCG-300 series. Transmit power depends on the version: 16 dBm in EU868 and 20 dBm in US915, with optional IN865, AS923, AU915 and KR920 settings. Receive sensitivity reaches -136 dBm in LoRa (spreading factor 12, bitrate 293 bps).

Power and environment. Power is supplied by two 3.6 V ER14505 AA batteries connected in parallel, not included. The operating voltage ranges from 3.1 V to 3.65 V, with a low battery threshold of 3.2 V. Standby current is 25 µA and typical wake-up current is 127 mA. At 25 °C with reports every 30 minutes, battery life is 5 years.

Typical uses. This meter suits three-phase power consumption monitoring, energy optimisation and preventive maintenance of equipment. It integrates into energy management and building automation systems, including remote meter reading.

Compliance. The product complies with the CE RED directive and FCC Part 15B.