D10163 – Single-phase DIN rail energy meter with current transformer

Single-phase DIN rail energy meter with current transformer

Current Transformers Sensors

  • Operation:-25~55℃
  • 100~275V
  • <1VA
  • 100A
Manufacturer part number
271894913
Manufacturer
Reallin
Temperature range
Operation:-25~55℃
Voltage Range
100~275V

Single-phase two-wire active energy meter for DIN rail mounting, measuring the consumption of a circuit through current transformers. It provides an RS485 link for remote reading.

Product overview

Overview. The Reallin D10163 is a single-phase two-wire active energy meter in DIN rail format, designed to measure the actual consumption of a load on a single-phase AC network with a rated frequency of 50 Hz. It is supplied with a current transformer measuring input.

Main characteristics. Rated voltage Un of 230 V, voltage range of 100 to 275 V, reference current Ib of 25 A, maximum current Imax of 100 A and minimum current Imin of 1.25 A. Accuracy class B/1.0 for active energy, pulse constant of 1000 imp/kWh, LED pulse indicator and dimensions of 18.5 × 66 × 110 mm for a weight of about 0.1 kg.

Interfaces and connectivity. RS485-A/B communication interface with screw-type terminals, allowing integration into a supervision system.

Power and environment. Current circuit apparent power below 1 VA at Ib, and voltage circuit below 2.4 W and 6 VA at Un. Protection degree IP 20, insulation class II, operating temperature range -25 to 55 °C.

Standards. Compliant with EN 50470-3:2022 and IEC 62052-31:2015.

Typical uses. Energy measurement and consumption monitoring in distribution boards and control cabinets, particularly for sharing consumption across a single-phase network.

Integration. Direct mounting on a standard DIN rail, without screw fixing, for series deployment in compact spaces.

See all specifications

Highlights

  • Accuracy: Class B/1.0 for active
  • Communication interface: RS485-A/B with screw type
  • Current circuit apparent power at Ib: <1VA
  • Dimension(LxWxD): 18.5×66×110mm
  • Insulation Class: II
  • Maximum current Imax: 100A

Typical applications

Derived from the part category, not a compatibility statement.

See also

Technical questions

Ask a question

No published question about this part yet. Questions are reviewed before publication.