Single-phase two-wire active energy meter for DIN rail mounting, measuring the consumption of a circuit through current transformers. It provides an RS485 link for remote reading.
Temperature rangeOperation:-25~55℃
Voltage Range100~275V
Communication interfaceRS485-A/B with screw type
Current circuit apparent power at Ib<1VA
Maximum current Imax100A
Minimum Current (Imin)1.25A
Product overview
Overview. The Reallin D10163 is a single-phase two-wire active energy meter in DIN rail format, designed to measure the actual consumption of a load on a single-phase AC network with a rated frequency of 50 Hz. It is supplied with a current transformer measuring input.
Main characteristics. Rated voltage Un of 230 V, voltage range of 100 to 275 V, reference current Ib of 25 A, maximum current Imax of 100 A and minimum current Imin of 1.25 A. Accuracy class B/1.0 for active energy, pulse constant of 1000 imp/kWh, LED pulse indicator and dimensions of 18.5 × 66 × 110 mm for a weight of about 0.1 kg.
Interfaces and connectivity. RS485-A/B communication interface with screw-type terminals, allowing integration into a supervision system.
Power and environment. Current circuit apparent power below 1 VA at Ib, and voltage circuit below 2.4 W and 6 VA at Un. Protection degree IP 20, insulation class II, operating temperature range -25 to 55 °C.
Standards. Compliant with EN 50470-3:2022 and IEC 62052-31:2015.
Typical uses. Energy measurement and consumption monitoring in distribution boards and control cabinets, particularly for sharing consumption across a single-phase network.
Integration. Direct mounting on a standard DIN rail, without screw fixing, for series deployment in compact spaces.
Single-phase two-wire active energy meter for DIN rail mounting, measuring the consumption of a circuit through current transformers. It provides an RS485 link for remote reading.
Temperature rangeOperation:-25~55℃
Voltage Range100~275V
Communication interfaceRS485-A/B with screw type
Current circuit apparent power at Ib<1VA
Maximum current Imax100A
2. Datasheet extract (recorded values)
Parameter
Value
Accuracy
Class B/1.0 for active
Communication interface
RS485-A/B with screw type
Current circuit apparent power at Ib
<1VA
Dimension(LxWxD)
18.5×66×110mm
Insulation Class
II
Maximum current Imax
100A
Minimum Current (Imin)
1.25A
Protection degree
IP 20
Pulsating Indicator
LED
Pulsating(meter constant)
1000imp/kWh
Rated Frequency Fn
50Hz±1.75%
Rated Voltage Un
230V
Reference current Ib
25A
Standards
EN 50470-3:2022,IEC 62052-31:2015
Temperature range
Operation:-25~55℃
Voltage circuit active/apparent power at Un
<2.4W/6VA
Voltage Range
100~275V
Weight Of Meter
About 0.1kg
Applications and use cases
Architectures in which 271894913 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
Associated system blocks
Energy metersCurrent sensorsData collection
Need a complete solution?
Send a request for 271894913 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productReallin
271894913
Single-phase DIN rail energy meter with current transformer
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.