Single-phase 230 V energy meter for DIN rail mounting, measuring active and reactive energy, with an RS485 interface for remote reading. Suited to individual metering.
Temperature rangeOperation:-30~70℃; Storage:-40~85℃
Voltage Range80%Un~120%Un
Current circuit apparent power at Ib<1VA
Maximum current Imax65A
Minimum Current (Imin)0.25A
Reference current Ib5A
Product overview
Overview. The Reallin D1006-BF is a single-phase 230 V two-wire energy meter designed for DIN rail mounting. It measures active and reactive energy.
Main characteristics. Accuracy is Class B/1.0 for active energy and Class 2.0 for reactive energy. The reference current Ib is 5 A and the maximum current Imax is 65 A, with a minimum current of 0.25 A and a starting current of 0.4% Ib. The pulse constant is 1000 imp/kWh and 1000 imp/kvarh. The 6+4 digit LCD display is complemented by an LED pulse indicator. Rated voltage is 230 V/240 V, voltage range 80% to 120% Un, rated frequency 50/60 Hz.
Interfaces and connectivity. The RS485 communication interface with screw terminals supports speeds up to 115200 bps for remote reading.
Power and environment. Power consumption is below 1.5 W and 8 VA in the voltage circuit, and below 1 VA in the current circuit at Ib. The operating temperature range is -30 to 70 °C, the storage range -40 to 85 °C. Protection degree is IP51 in a protective enclosure, insulation class II. Dimensions 90 × 35 × 62 mm, weight about 0.13 kg.
Standards. The meter complies with EN 50470-3:2022, IEC 62053-21/23:2020, IEC 62052-11:2020, IEC 62052-31:2015, UL61010-1 and UL61010-2-030.
Typical uses. Individual or sub-system metering and sub-billing. The RS485 interface allows integration into a supervision system or with PLCs via Modbus.
Single-phase 230 V energy meter for DIN rail mounting, measuring active and reactive energy, with an RS485 interface for remote reading. Suited to individual metering.
Temperature rangeOperation:-30~70℃; Storage:-40~85℃
Voltage Range80%Un~120%Un
Current circuit apparent power at Ib<1VA
Maximum current Imax65A
Minimum Current (Imin)0.25A
2. Datasheet extract (recorded values)
Parameter
Value
Accuracy
Class B/1.0 for active; Class 2.0 for reactive
Communication interface
RS485 with screw type,maximum upto 115200bps
Current circuit apparent power at Ib
<1VA
Dimension(LxWxD)
90×35×62mm
Insulation Class
II
LCD display
6+4 digits
Maximum current Imax
65A
Minimum Current (Imin)
0.25A
Protection degree
IP51 in protectve enclosure
Pulsating Indicator
LED
Pulsating(meter constant)
1000imp/kWh; 1000imp/kvarh
Rated Frequency Fn
50/60Hz
Rated Voltage Un
230V/240V
Reference current Ib
5A
Standards
EN 50470-3:2022,IEC 62053-21/23:2020,IEC 62052-11:2020,; IEC 62052-31:2015,UL61010-1,UL61010-2-030
Starting Current (Ist)
0.4%Ib
Temperature range
Operation:-30~70℃; Storage:-40~85℃
Voltage circuit active/apparent power at Un
<1.5W/8VA
Voltage Range
80%Un~120%Un
Weight Of Meter
About 0.13kg
Applications and use cases
Architectures in which 284106465 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
Solar panels produce most when nobody is home, and the surplus goes to the grid. A battery with its inverter stores this energy and returns it in the evening, with a meter measuring what the home draws
To check
Panel power and the inverter compatibility of the battery
Usable capacity compared with the evening and night consumption
Local grid connection rules for balcony and home systems
Associated system blocks
InvertersBatteryMetering
Need a complete solution?
Send a request for 284106465 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productReallin
284106465
Single-phase 230 V DIN rail energy meter, active and reactive
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details