Overview. The Seeed Studio non-invasive AC current transformer 50A-1V is a current transformer (CT) sensor for measuring alternating current without interrupting the circuit. It is installed by clamping it around the target conductor.
Main characteristics. Rated input of 50 A AC for a rated output of 1 V, with an accuracy of 1%. The open size is 13 mm x 13 mm. Dimensions are 78 mm x 62 mm x 26 mm for a weight of 71 g, and the leading wire is 1 m long.
Isolation and environment. The dielectric strength between output and housing is AC 3.5 kV for 1 min at 50 Hz, providing galvanic isolation of the output. The working temperature range is -25 ℃ to +70 ℃. The waterproof grade is IP00 and the battery is excluded.
Typical uses. AC current measurement, monitoring and protection of AC motors, lighting equipment and air compressors.
Integration. Tool-free installation without modifying the wiring, suitable for space-constrained environments.
Architectures in which 101990063 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
Associated system blocks
Energy metersCurrent sensorsData collection
Need a complete solution?
Send a request for 101990063 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.