The Sino-Inst DC-M100 is a digital gas mass flow controller and meter for a 30 to 100 SLM (N2) range, with 0-5V, 4-20mA or RS485 outputs and 24V DC power.
Control range2%-100%/2%-100%
Frame Of Flow MetersStainless Steel And PTFE Flow Meters
Accuracy≤+1.0%F.S
Response time≤2sec
Communication Signal0-5V/4-20mA/RS485
Connector size3mm, 6mm, 10mm, 1/4. 3/8 etc.
Product overview
Overview. The Sino-Inst DC-M100 is a digital gas mass flow controller and meter, available as the DC-M100C controller and the DC-M100M flow meter, covering a 30 SLM to 100 SLM range for nitrogen (N2).
Performance. Accuracy ≤+1.0% F.S, linearity ≤±0.5% F.S, repeatability ≤+0.2% F.S and response time ≤2 sec. Standard conditions are 20C and 101325 Pa, with mass flow expressed in SCCM or SLM.
Interfaces and connectivity. Analog outputs 0-5V and 4-20mA, plus an RS485 serial link. Power supply 24V DC. Connector sizes 3mm, 6mm, 10mm, 1/4 and 3/8.
Pressure and sealing. Maximum pressure resistance 50 Bar, leakage rate 1×10-9 atm.cc/sec He, and a normally closed valve.
Typical uses. Gas flow measurement and control in industrial processes, with PLC integration via the RS485 link or the analog signals.
No published question about this part yet. Questions are reviewed before publication.
Complete specifications
Every characteristic recorded for DC-M100 DIGITAL FLOW CONTROLLER/FLOW METER, with where it comes from. Use the filters to find one quickly.
All specifications (19)
Characteristic
Value
Response time
≤2sec
Accuracy
≤+1.0%F.S
Communication Signal
0-5V/4-20mA/RS485
Connector size
3mm, 6mm, 10mm, 1/4. 3/8 etc.
Control range
2%-100%/2%-100%
Flow range (N2):
30SLM—100SLM
Frame Of Flow Meters
Stainless Steel And PTFE Flow Meters
Gas Mass Flow Meters
Applications, Benefits, And Top Manufacturers
Leakage rate
1×10-9atm.cc/sec He
Linearity
≤±0.5%F.S
Mass flow unit
SCCM (standard milliliters per minute) SLM (standard liters per minute)
Maximum pressure resistance:
50Bar
Power supply method
24V DC
Product brand
Sino-Inst
Product Model
DC-M100C / DC-M100M
Product SKU
DC-M100 Digital Flow Controller/Flow Meter
Repeatability
≤+0.2%F.S
Standard conditions
Temperature: -293.15K (20C) Pressure: -101325Pa (760mmHg) F.S (Full Scale) means full scale
Valve type
Normally closed valve
No specification matches.
Last verification : 2026-11-02
Technical documentation
Official documents and the technical data recorded for DC-M100 DIGITAL FLOW CONTROLLER/FLOW METER. For a missing document or a specific revision, our experts send it to you.
The Sino-Inst DC-M100 is a digital gas mass flow controller and meter for a 30 to 100 SLM (N2) range, with 0-5V, 4-20mA or RS485 outputs and 24V DC power.
Control range2%-100%/2%-100%
Frame Of Flow MetersStainless Steel And PTFE Flow Meters
Accuracy≤+1.0%F.S
Response time≤2sec
Communication Signal0-5V/4-20mA/RS485
2. Datasheet extract (recorded values)
Parameter
Value
Response time
≤2sec
Accuracy
≤+1.0%F.S
Communication Signal
0-5V/4-20mA/RS485
Connector size
3mm, 6mm, 10mm, 1/4. 3/8 etc.
Control range
2%-100%/2%-100%
Flow range (N2):
30SLM—100SLM
Frame Of Flow Meters
Stainless Steel And PTFE Flow Meters
Gas Mass Flow Meters
Applications, Benefits, And Top Manufacturers
Leakage rate
1×10-9atm.cc/sec He
Linearity
≤±0.5%F.S
Mass flow unit
SCCM (standard milliliters per minute) SLM (standard liters per minute)
Maximum pressure resistance:
50Bar
Power supply method
24V DC
Product brand
Sino-Inst
Product Model
DC-M100C / DC-M100M
Product SKU
DC-M100 Digital Flow Controller/Flow Meter
Repeatability
≤+0.2%F.S
Standard conditions
Temperature: -293.15K (20C) Pressure: -101325Pa (760mmHg) F.S (Full Scale) means full scale
Valve type
Normally closed valve
Applications and use cases
Architectures in which DC-M100 DIGITAL FLOW CONTROLLER/FLOW METER can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Answers to the questions that the recorded characteristics of DC-M100 DIGITAL FLOW CONTROLLER/FLOW METER can answer. A question is not asked when nothing is recorded to answer it.
1Does it support RS-485?
Yes — recorded under "Communication Signal": 0-5V/4-20mA/RS485.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details