UT-10-12 – DC power surge protector for 12 to 200 VDC supply

DC power surge protector for 12 to 200 VDC supply

Surge Protectors

Manufacturer part number
PRO_VIEW-334
Manufacturer
UOTEK

UOTEK class C DC surge protector for DC power distribution systems, protecting equipment against lightning-induced and switching transient overvoltages.

Product overview

Overview. The UOTEK UT-10-12 DC power surge protector is a class C protector for DC power distribution systems, protecting electrical and electronic equipment against lightning electromagnetic pulse induced voltages, operating transients and resonance overvoltages (<100 µs). The UT-10-12 reference designates the model within the UT-10-12/UT-10-24/UT-40-48/UT-40-200 series.

Main characteristics. Nominal operating voltage (Un) of 12 VDC, maximum operating voltage of 24 VDC to 30 VDC, nominal discharge current (In) of 5 kA, maximum flow capacity (Imax) of 10 kA, protection level (Up) of 1200 V or less, response time (tA) of 25 ns. Preposed fuse 40 AgL/gG, protection mode +/PE, -/PE.

Interfaces and signalling. Optional remote signal contacts NC-COM, COM, NO-COM, green indicator for normal operation and red indicator for failure.

Power and environment. Operating temperature from -40 to +85 °C, relative humidity 95 % or less (25 °C), height 3 km or less, protection level IP20, flame retardant level V0/red.

Typical uses. Protection of telecommunication, industrial control, security and transport equipment powered by DC supply.

Integration. 35 mm DIN rail installation. Dimensions 90 × 36 × 65 mm. Access wire area of 6 mm² or more, at least 4 mm².