A2S – Wireless heat detector with thermistor and rate-of-rise element

Wireless heat detector with thermistor and rate-of-rise element

Smoke and Flame Detectors

  • 2026-09-16 15:30
Manufacturer part number
A2S
Manufacturer
Wanlin
Published
2026-09-16 15:30
Release date
2026-09-16

Wanlin A2S wireless heat detector with an NTC thermistor element and a dual fixed temperature and rate-of-rise algorithm, for indoor fire detection.

Product overview

Overview. The Wanlin A2S wireless heat detector is a wireless heat detector designed for fire detection. It combines a fixed temperature algorithm and a rate-of-rise algorithm, evaluated on a thermistor bridge with air-flow compensation.

Main characteristics. Accuracy class to EN 54-5 and GB 4716, with a thermistor tolerance of ±1.5 °C. Fixed temperature threshold between 54 and 70 °C depending on the class, and rate-of-rise trip between 3 and 30 °C/min. Static response time of 30 to 120 s to the EN 54-5 test regime. Coverage up to 50 m² at 6 m mounting height, and 30 m² in high-ceiling or high-airflow areas.

Interfaces and connectivity. 433 MHz FSK, LoRaWAN 1.0.3 Class A or 4G LTE Cat-1 uplink depending on the reference. A fault and tamper uplink is sent every 24 h. Integral 80 dB(A) sounder at 3 m, with platform alert and group alarm through the paired gateway.

Power and environment. 3.6 V ER18505M lithium cell, 5-year service life, field-replaceable (3 years for the 4G version). Consumption of 11 µA standby, 120 mA peak transmit and 28 mA in alarm. Operating range of -10 to +55 °C (down to -30 °C for the wide-temperature version), humidity 10 to 95 % RH non-condensing. Protection rating IP42 as standard, IP65 for the sealed industrial housing.

Typical uses. Fire detection in residential premises, offices, warehouses and kitchens, particularly where cabling is difficult to install.

Housing and dimensions. Flame-retardant ABS V-0 housing, or polycarbonate with a stainless-steel heat collector for the IP65 version. Diameter 100 mm, height 46 mm, weight 152 g including the cell.

Certifications. EN 54-5, CE, RoHS, REACH, FCC Part 15 and GB 4716 CCCF. EN 14604 is available on request for the residential version.

See all specifications

Highlights

  • Humidity range: 10-95% RH non-condensing, conformal-coated PCB on the IP65 SKU
  • Operating temperature: -10 deg C to +55 deg C, wide-temp SKU to -30 deg C for cold stores
  • Dimensions/Weight: 100 mm diameter x 46 mm height, 152 g net including the cell
  • Power consumption: 11 uA standby, 120 mA peak transmit, 28 mA in alarm
  • Published: 2026-09-16 15:30
  • Release date: 2026-09-16