EN_54
Addressable EN 54-5 heat detector with dual thermistor

- Cost Layer — USD per piece
- USD for 5000 pcs
- Published
- 2026-09-10 14:00
- Release date
- 2026-09-10
Addressable EN 54-5 heat detector with dual thermistor
The Wanlin WLF-HD200 is an addressable heat detector compliant with EN 54-5, combining rate-of-rise and fixed-temperature detection for fire detection installations.
Overview. The Wanlin WLF-HD200 is an addressable heat detector from the Wanlin EN 54 series, designed for fire detection according to EN 54-5. It combines a rate-of-rise and fixed-temperature algorithm, with four threshold classes selectable per SKU.
Main characteristics. The sensor pairs a dual NTC thermistor with rate-of-rise differentiation and a fixed 57 °C, 65 °C or 78 °C threshold element. Alarm classes are A1R (54-65 °C), A2S (54-70 °C), BR (65-85 °C) and CS (84-100 °C) per EN 54-5. Coverage reaches 50 m² at a 6 m mounting height, and 30 m² in high-airflow kitchens and laundry rooms. A contamination pre-warning is included.
Interfaces and connectivity. The detector runs on a proprietary addressable loop protocol compatible with EN 54-13, powered at 15-28 V DC, with 38 µA standby current and 3.8 mA in alarm state, supporting 127 devices per loop circuit. An optional open gateway supports Modbus or BACnet. A 24 V DC conventional variant is available. It is compatible with the EN 54-17 isolator base. An optional EN 54-3 sounder base delivers 85 dB(A) at 3 m.
Power and environment. The operating range is -20 °C to +80 °C as standard, and up to +100 °C for the CS variant. Permitted humidity is 10 to 95 % RH non-condensing. The protection rating is IP42 as standard and IP65 for the stainless-steel variant intended for kitchens, boiler rooms and food plants, the latter rated to 98 % RH.
Housing and dimensions. The flame-retardant ABS V-0 housing measures 100 mm in diameter by 48 mm in height, for a net weight of 112 g. A stainless-steel option is offered for food processing and marine areas.
Typical uses. This detector suits fire detection in commercial buildings, kitchens, laundry rooms and technical rooms, as well as installations subject to EN 54 and CE marking under CPR (EU) 305/2011.
Integration. Stated certifications include EN 54-5, EN 54-13, CE, RoHS and REACH, with VdS and LPCB listed and FM on request. Products are available on quotation from Atlas Electronics.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for EN_54, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| IP rating | IP42 indoor standard, IP65 stainless-steel variant for kitchens, boiler rooms and food plants |
| Humidity range | 10-95% RH non-condensing, IP65 variant rated to 98% RH |
| Additional Features | Rate-of-rise plus fixed-temperature dual algorithm, selectable class per SKU, contamination pre-warning, EN 54-17 isolator base compatible |
| Alarm Threshold | EN 54-5 class A1R (54-65 deg C) / A2S (54-70 deg C) / BR (65-85 deg C) / CS (84-100 deg C) selectable by SKU |
| Certifications | CE (CPR EU 305/2011) / EN 54-5 / EN 54-13 / RoHS / REACH / WEEE / VdS / LPCB / FM on request |
| Cost Layer — USD per piece | USD for 5000 pcs |
| Coverage Area | Up to 50 m2 at 6 m mounting height per EN 54-5, 30 m2 in high-airflow kitchens and laundry rooms |
| Detection Principle | Addressable rate-of-rise plus fixed-temperature heat detection per EN 54-5, four thermistor threshold classes |
| Dimensions/Weight | 100 mm diameter x 48 mm height, 112 g net weight |
| Housing Material | Flame-retardant ABS V-0 housing, stainless-steel option for food processing and marine areas |
| Loop / Interconnect Protocol | Proprietary addressable loop protocol, EN 54-13 compatible, optional open gateway (Modbus / BACnet) |
| Operating Temperature | -20 deg C to +80 deg C standard, class CS variant rated to +100 deg C |
| Power supply | Loop-powered 15-28V DC addressable loop; 24V DC conventional variant available |
| Product description | EN 54-5 heat detector EN 54-5 Addressable Heat Detector export OEM ODM wholesale |
| Published | 2026-09-10 14:00 |
| Reference | www.wanlinfire.com / WLF-HD200 / EN 54 series under CPR (EU) 305/2011 / EN 54-13 / EN 54-21 / RoHS REACH WEEE |
| Release date | 2026-09-10 |
| Sensor Element | Dual NTC thermistor pair with rate-of-rise differentiation and fixed 57 deg C / 65 deg C / 78 deg C threshold element |
| Sound Output | No integral sounder in base model; optional EN 54-3 sounder base delivering 85 dB(A) at 3 m |
| Standby Current | 38 uA standby, 3.8 mA alarm state, 127 devices supported per loop circuit |
| Strategic OEM Partner — USD 320,000+ — 32% off list — Multi- country | Dedicated engineering team, joint roadmap, 18-month price lock |
| Target buyer | EU importer, fire contractor, MEP consultant, system integrator, facility manager, distributor, public tender bidder |
No specification matches.
Last verification : 2026-11-03
Official documents and the technical data recorded for EN_54. For a missing document or a specific revision, our experts send it to you.
The Wanlin WLF-HD200 is an addressable heat detector compliant with EN 54-5, combining rate-of-rise and fixed-temperature detection for fire detection installations.
| Parameter | Value |
|---|---|
| IP rating | IP42 indoor standard, IP65 stainless-steel variant for kitchens, boiler rooms and food plants |
| Humidity range | 10-95% RH non-condensing, IP65 variant rated to 98% RH |
| Additional Features | Rate-of-rise plus fixed-temperature dual algorithm, selectable class per SKU, contamination pre-warning, EN 54-17 isolator base compatible |
| Alarm Threshold | EN 54-5 class A1R (54-65 deg C) / A2S (54-70 deg C) / BR (65-85 deg C) / CS (84-100 deg C) selectable by SKU |
| Certifications | CE (CPR EU 305/2011) / EN 54-5 / EN 54-13 / RoHS / REACH / WEEE / VdS / LPCB / FM on request |
| Cost Layer — USD per piece | USD for 5000 pcs |
| Coverage Area | Up to 50 m2 at 6 m mounting height per EN 54-5, 30 m2 in high-airflow kitchens and laundry rooms |
| Detection Principle | Addressable rate-of-rise plus fixed-temperature heat detection per EN 54-5, four thermistor threshold classes |
| Dimensions/Weight | 100 mm diameter x 48 mm height, 112 g net weight |
| Housing Material | Flame-retardant ABS V-0 housing, stainless-steel option for food processing and marine areas |
| Loop / Interconnect Protocol | Proprietary addressable loop protocol, EN 54-13 compatible, optional open gateway (Modbus / BACnet) |
| Operating Temperature | -20 deg C to +80 deg C standard, class CS variant rated to +100 deg C |
| Power supply | Loop-powered 15-28V DC addressable loop; 24V DC conventional variant available |
| Product description | EN 54-5 heat detector EN 54-5 Addressable Heat Detector export OEM ODM wholesale |
| Published | 2026-09-10 14:00 |
| Reference | www.wanlinfire.com / WLF-HD200 / EN 54 series under CPR (EU) 305/2011 / EN 54-13 / EN 54-21 / RoHS REACH WEEE |
| Release date | 2026-09-10 |
| Sensor Element | Dual NTC thermistor pair with rate-of-rise differentiation and fixed 57 deg C / 65 deg C / 78 deg C threshold element |
| Sound Output | No integral sounder in base model; optional EN 54-3 sounder base delivering 85 dB(A) at 3 m |
| Standby Current | 38 uA standby, 3.8 mA alarm state, 127 devices supported per loop circuit |
| Strategic OEM Partner — USD 320,000+ — 32% off list — Multi- country | Dedicated engineering team, joint roadmap, 18-month price lock |
| Target buyer | EU importer, fire contractor, MEP consultant, system integrator, facility manager, distributor, public tender bidder |
Answers to the questions that the recorded characteristics of EN_54 can answer. A question is not asked when nothing is recorded to answer it.
Yes — recorded under "Loop / Interconnect Protocol": Proprietary addressable loop protocol, EN 54-13 compatible, optional open gateway (Modbus / BACnet).
-20 deg C to +80 deg C standard, class CS variant rated to +100 deg C (source: Operating Temperature).
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Addressable EN 54-5 heat detector with dual thermistor

Smart Liquid Solid Radar Level Meter Dust Smoke Environment

Smoke Sensor

Smoke Alertor with LoRa Technology

Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | EN_54 |
| Manufacturer | Wanlin |
Smoke and Flame Detectors
Electro-optical UV and infrared wide-angle flame detector
Price on request
Smoke and Flame Detectors
Intelligent Event Detection Server for Traffic, 32 Channels · Ref. : IVS-TB9000-4K-TS2
Price on request
Smoke and Flame Detectors
Zigbee smoke detector with 85 dB audible alarm · Ref. : SD324
Price on request
Smoke and Flame Detectors
Zigbee 3.0 ceiling-mount smoke detector
Price on request
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details