The ABH210 gas detection transmitter from WG Sensor measures CO, H2S, O2 and combustible gases (LEL) and sends the reading over 4-20mA or RS-485 for industrial site monitoring.
Accuracy≤±5% F.S.
Response time≤60 S
CO0-1000ppm
CO — 0-1000ppm — 50ppm — 150ppm1/0.1ppm
EX0-100% LEL
EX — 0-100% LEL — 20% LEL — 50% LEL1/0.1% LEL
Product overview
Overview. The ABH210 gas detection transmitter from WG Sensor is a device in the Environmental and Gas Sensors category. It measures carbon monoxide (CO) over 0 to 1000 ppm, hydrogen sulfide (H2S) over 0 to 100 ppm, oxygen (O2) over 0 to 30 %VOL and combustible gases over 0 to 100% LEL.
Measurement characteristics. Response time is 60 s or less and accuracy is within ±5% F.S. Resolution is 1 ppm for CO, 0.1 ppm for H2S, 0.1% LEL for combustible gases and 0.1% VOL for O2. Alarm set points are adjustable, with a low and a high point for each gas.
Connectivity and display. The device provides a 4-20mA output and an RS-485 output using the industry standard signal. It has a high-definition LCD screen, an infrared remote control, and alarm, fault and running indicator lights.
Power and environment. The power supply is DC 12V-28V at 500mA. Standby time is 8 hours of continuous operation after a full charge. The protection rating is Ip66 and the housing is die-cast aluminum, explosion-proof and anti-corrosion. The operating temperature range is -20ºC to +50ºC, with humidity below 95%RH without condensation. The unit weighs less than 1.6 kg.
Certification. It is marked Ex II 2G Ex db IIC T6 Gb and complies with GB15322.1-2019.
Typical uses. The transmitter suits monitoring of sites exposed to gas leaks, such as urban gas distribution networks, refineries and chemical plants. Its RS-485 output allows connection to a PLC or DCS for remote detection, control and alarm.
The ABH210 gas detection transmitter from WG Sensor measures CO, H2S, O2 and combustible gases (LEL) and sends the reading over 4-20mA or RS-485 for industrial site monitoring.
Accuracy≤±5% F.S.
Response time≤60 S
CO0-1000ppm
CO — 0-1000ppm — 50ppm — 150ppm1/0.1ppm
EX0-100% LEL
2. Datasheet extract (recorded values)
Parameter
Value
Response time
≤60 S
Accuracy
≤±5% F.S.
CO
0-1000ppm
CO — 0-1000ppm — 50ppm — 150ppm
1/0.1ppm
EX
0-100% LEL
EX — 0-100% LEL — 20% LEL — 50% LEL
1/0.1% LEL
Ex grade
II 2G Ex db IIC T6 Gb
Explosion
GB15322.1-2019 (The first part of combustible gas detection alarm:
Gas Type
range
Gas type — range — Low alarm point — High alarm point
Resolution
H2S
0-100ppm
H2S — 0-100ppm — 10ppm — 35ppm
1/0.1ppm
Indication mode:
high definition LCD screen
O2 — (0~30)%VOL — 19.5%VOL — 23.5%VOL
0.1% VOL
Output
4-20mA / RS485
-proof mark
measuring range of 0-100% LEL point type combustible gas detector)
Protection Level
Ip66
Shell material
Die-cast aluminum, explosion-proof and anti-corrosion
Standby time:
continuously 8 hours working after full charge
Weight
less than 1.6kg
Working Environment
Temperature -20ºC~+50ºC; humidity <95%RH condensation
Working voltage
DC 12V-28V 500mA
Applications and use cases
Architectures in which ABH210 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Offices and classrooms get stuffy without anyone measuring why. Indoor air quality monitoring places CO2, VOC and particle sensors in the rooms and reports their values through a gateway, so ventilation can be adjusted to real occupancy
To check
Parameters to measure (CO2 alone or CO2, VOC and particles)
Battery-powered sensors or mains-powered sensors with display
Integration with the ventilation control or building management system
Associated system blocks
Air sensorsGateway
Need a complete solution?
Send a request for ABH210 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details