Semiconductor R32 refrigerant gas detection module for leak detection in air conditioning and refrigeration systems. PWM output, 5000 ppm alarm point.
Operating Temperature0~50℃
Detection rangeAlarm value 5000ppm
Working current≤ 80mA
Storage humidity≤ 60%RH
Storage Temperature-20~60℃
Alarm Point5000ppm
Product overview
Overview. The Winsen ZP201 is an R32 refrigerant gas detection module built around a multi-layer thick film semiconductor gas sensor element with a filter adsorption layer, designed for refrigerant leak detection in air conditioning and refrigeration systems.
Main characteristics. The alarm point is set at 5000 ppm. The module is aged and factory calibrated, offers high sensitivity and fast response, and includes sensor fault self-diagnosis. Its filter adsorption layer reduces interference from alcohol and other gases. It weighs 5 g and measures 25×34×14.1.
Interfaces and output. The data output is PWM; an external pull-up resistor must be connected to the PWM signal.
Power and environment. The working voltage is 5.0±0.2 V DC, with no voltage reverse connection protection, and the working current is at most 80 mA. Warm-up time is at most 3 min. The operating temperature range is 0 to 50 °C at up to 95 %RH. Storage is between −20 and 60 °C at up to 60 %RH.
Typical uses. Detection of R32 refrigerant leaks in air conditioning and refrigeration installations.
Integration. An external pull-up resistor is required on the PWM output; the module must be supplied with 5 V DC without reverse polarity protection.
Semiconductor R32 refrigerant gas detection module for leak detection in air conditioning and refrigeration systems. PWM output, 5000 ppm alarm point.
Operating Temperature0~50℃
Detection rangeAlarm value 5000ppm
Working current≤ 80mA
Storage humidity≤ 60%RH
Storage Temperature-20~60℃
2. Datasheet extract (recorded values)
Parameter
Value
Alarm Point
5000ppm
Characteristics
Air conditioning and refrigeration system refrigerant leakage detection
Detection Principle
Module,semiconductor
Detection range
Alarm value 5000ppm
Model
ZP201
Notes
PWM signal output needs to be connected with external pull-up resistor
Operating Humidity
≤ 95%RH
Operating Temperature
0~50℃
Output data
PWM
Size
25×34×14.1
Storage humidity
≤ 60%RH
Storage Temperature
-20~60℃
Target
Refrigerant gas R32
Target gas
Refrigerant gas R32
Warm-Up Time
≤ 3 min
Weight
5g
Working Conditions
Working voltage 5±0.2V; Output PWM
Working current
≤ 80mA
Working voltage
5.0±0.2V DC (No voltage reverse connect protection)
Integration
Points to check before using ZP201 in a design. They are derived from the recorded characteristics, not from the manufacturer's application circuits.
1Thermalrated operating range 0~50℃ — check it against the installation environment.
Power and communication
Working current
≤ 80mA
Working voltage
5.0±0.2V DC (No voltage reverse connect protection)
Check the exact pin assignment and the application circuit in the datasheet, or ask our experts.
Implementation checklist
Thermal : rated operating range 0~50℃ — check it against the installation environment.
Applications and use cases
Architectures in which ZP201 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productWinsen
ZP201
R32 refrigerant gas detection module with PWM output
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.