The GCAN-IO-8000 is a CANopen PLC slave I/O coupler with up to 32 pluggable I/O modules, up to 8 points per module, for connecting inputs and outputs over a CAN bus.
CAN — interfaceone open 4 terminal
Starting Currentabout 2.5 times continuous current
Overview. The GCAN-IO-8000 from GCAN is a PLC I/O coupler of the slave station type, designed to extend a controller's inputs and outputs over a CAN bus. It accepts up to 32 pluggable I/O modules, for a maximum of 32 × 8 I/O points.
Main characteristics. The module provides 1500 Vrms electrical isolation, a baud rate from 10K to 1000K and supports 1 to 127 nodes on the network. Its dimensions are 100 mm × 69 mm × 48 mm and its IP rating is IP20.
Interfaces and communication. The CAN interface is one open 4-terminal port. The supported protocol is CANopen. Programming is carried out in the OpenPCS environment, conforming to the IEC 61131-3 standard.
Power and environment. The module operates from 24V DC (18 to 36V). The power contacts are rated at a maximum of 24V DC and 10A. The starting current is about 2.5 times the continuous current. The working temperature range is -40℃ to +85℃, at 0 to 90% RH, without condensation.
Typical uses. This coupler suits extending the inputs and outputs of a programmable controller over a CANopen network, in control cabinets exposed to varying temperatures and humidity.
Integration. The GCAN-IO-8000 connects to the system's CAN bus and is configured with the OpenPCS tool. Available on quotation from Atlas Electronics.
The GCAN-IO-8000 is a CANopen PLC slave I/O coupler with up to 32 pluggable I/O modules, up to 8 points per module, for connecting inputs and outputs over a CAN bus.
CAN — interfaceone open 4 terminal
Starting Currentabout 2.5 times continuous current
Baud rate10K~1000K
Dimension100mm*69 mm*48 mm
Electrical isolation1500 Vrms
2. Datasheet extract (recorded values)
Parameter
Value
Baud rate
10K~1000K
CAN — interface
one open 4 terminal
Dimension
100mm*69 mm*48 mm
Electrical isolation
1500 Vrms
Insert I/O Module
32 pieces (Maximum 32*8 IO points)
IP Grade
IP20
Module type
PLC Slave station
Number of nodes
1~127
Power contacts
maximum 24V DC/maximum 10A
Programming Environment
OpenPCS (conform to IEC 61131-3 standard)
Protocol
CANopen
Starting Current
about 2.5 times continuous current
Supply / power
24V DC (18~36V)
Working temperature
-40℃~+85℃, 0~90%RH, without condensation
Applications and use cases
Architectures in which GCAN-IO-8000 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Every intervention on a remote machine means a trip on site. A 4G or 5G router with VPN gives the maintenance team secure access to the PLC and the operator panel from the office
To check
VPN type and how access rights are granted and removed
Mobile coverage at the machine site
Separation between the machine network and the customer network
A proprietary PLC locks the project into one vendor’s tools. Industrial controllers built on the Raspberry Pi Compute Module run Linux, Node-RED, Python or CODESYS on DIN rail, with I/O modules, an operator panel and a cellular router for remote access
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details