The GCAN-IO-8100 is a GCAN slave PLC I/O coupler with up to 32 plug-in I/O modules and a CAN interface, used to extend a controller over Modbus TCP/RTU.
CAN — interfaceone open 4 terminal
Starting Currentabout 2.5 times continuous current
Overview. The GCAN-IO-8100 from GCAN is a slave PLC coupler that accepts up to 32 plug-in I/O modules, for a maximum of 32 × 8 input-output points, to extend the capacity of a programmable logic controller.
Main characteristics. The module measures 100 mm × 69 mm × 48 mm and has an IP20 protection rating. It is programmed with the OpenPCS environment, conforming to the IEC 61131-3 standard.
Interfaces and connectivity. The coupler provides one open 4-terminal CAN interface and supports baud rates from 600 to 115200. It supports the Modbus TCP/RTU protocol and can handle 1 to 247 nodes. Electrical isolation of 1500 Vrms is provided.
Power and environment. The supply is 24 V DC (range 18 to 36 V). The power contacts are rated at maximum 24 V DC and maximum 10 A. The starting current is about 2.5 times the continuous current. The operating temperature range is -40 ℃ to +85 ℃, with 0 to 90 %RH humidity without condensation.
Typical uses and integration. With Modbus TCP/RTU support and its CAN interface, the GCAN-IO-8100 integrates into a controller network to acquire or drive remote inputs and outputs.
The GCAN-IO-8100 is a GCAN slave PLC I/O coupler with up to 32 plug-in I/O modules and a CAN interface, used to extend a controller over Modbus TCP/RTU.
CAN — interfaceone open 4 terminal
Starting Currentabout 2.5 times continuous current
Baud rate600~115200
Dimension100mm*69 mm*48 mm
Electrical isolation1500 Vrms
2. Datasheet extract (recorded values)
Parameter
Value
Baud rate
600~115200
CAN — interface
one open 4 terminal
Dimension
100mm*69 mm*48 mm
Electrical isolation
1500 Vrms
Insert I/O Module
32 pieces (Maximum 32*8 IO points)
IP Grade
IP20
Module type
PLC Slave station
Number of nodes
1~247
Power contacts
maximum 24V DC/maximum 10A
Programming Environment
OpenPCS (conform to IEC 61131-3 standard)
Protocol
Modbus TCP/RTU
Starting Current
about 2.5 times continuous current
Supply / power
24V DC (18~36V)
Working temperature
-40℃~+85℃, 0~90%RH, without condensation
Applications and use cases
Architectures in which GCAN-IO-8100 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Every intervention on a remote machine means a trip on site. A 4G or 5G router with VPN gives the maintenance team secure access to the PLC and the operator panel from the office
To check
VPN type and how access rights are granted and removed
Mobile coverage at the machine site
Separation between the machine network and the customer network
A proprietary PLC locks the project into one vendor’s tools. Industrial controllers built on the Raspberry Pi Compute Module run Linux, Node-RED, Python or CODESYS on DIN rail, with I/O modules, an operator panel and a cellular router for remote access
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details