The HXV8 is an outdoor pole-mounted vacuum circuit breaker for controlling and protecting 12 kV three-phase 50 Hz distribution overhead lines, with integrated sensors.
Temperature range-40℃~70℃
Auxiliary and Control Circuit — Rated Supply Voltage — VDC: 24 or Other
Energy Harvesting Sensor — Rated Primary Input Voltage — kV10kV/√3
Current Sensor — Phase Current (Ratio)600A/1V
Rated Phase-Opposition Breaking Current — kA17.4
Zero-Sequence Current (Accuracy Class)<1% (1%~120% In), Protection 10P10
Product overview
Overview. The Hexing HXV8 is an outdoor vacuum circuit breaker mounted on a pole, designed for controlling and protecting 12 kV three-phase 50 Hz distribution overhead lines. It suits distribution networks exposed to harsh environmental conditions and frequent operations.
Main characteristics. Rated phase-opposition breaking current of 17.4 kA, closing time of 30 to 70 ms and opening time of 20 to 60 ms. Rated operating sequence 0-0.3s-CO-180s-CO. Rated main circuit resistance of 80 μΩ or less and three-phase opening/closing non-simultaneity of 2 ms or less. Lightning impulse withstand voltage of 75/85 kV. Partial discharge of 20 pC or less at 1.1Ur.
Measurement and protection. Phase current sensor with a 600A/1V ratio, protection accuracy class 5P10 and metering class 0.5S, three-in-one compatible. Zero-sequence current sensor with a 20A/0.2V ratio, accuracy below 1% from 1% to 120% In, protection class 10P10. Phase voltage sensor with a (10kV/√3)/(3.25V/√3) ratio, class 0.5. Zero-sequence voltage sensor with a (10kV/√3)/(6.5V/√3) ratio, class 3P. Rated secondary output voltage AC 190V.
Power and environment. Auxiliary and control circuit rated supply voltage DC 24 V or other. Enclosure protection rating IP67. Temperature range -40 ℃ to 70 ℃. Low-power electromagnetic implementation and energy harvesting sensor with rated primary input voltage 10kV/√3.
Integration. Independent pillar structure per phase with adjustable phase spacing and fully enclosed insulation cast in weather-resistant outdoor epoxy resin. The current and voltage measurements support line supervision and protection; compatibility with protection systems should be checked for each project.
The HXV8 is an outdoor pole-mounted vacuum circuit breaker for controlling and protecting 12 kV three-phase 50 Hz distribution overhead lines, with integrated sensors.
Temperature range-40℃~70℃
Auxiliary and Control Circuit — Rated Supply Voltage — VDC: 24 or Other
Energy Harvesting Sensor — Rated Primary Input Voltage — kV10kV/√3
Current Sensor — Phase Current (Ratio)600A/1V
Rated Phase-Opposition Breaking Current — kA17.4
2. Datasheet extract (recorded values)
Parameter
Value
Auxiliary and Control Circuit — Rated Supply Voltage — V
DC: 24 or Other
Closing speed (6 mm before contact touch) — m/s
0.8 ± 0.2
Closing Time — ms
30 ~ 70
Current Sensor — Phase Current (Ratio)
600A/1V
DC Component Percentage
52%
Enclosure Protection Rating of Circuit Breaker
IP67
Energy Harvesting Sensor — Rated Primary Input Voltage — kV
10kV/√3
Implementation Method
Low-Power Electromagnetic Type
Lightning Impulse Withstand Voltage (Phase-to-Phase, Phase-to-Ground/Across Open Contact) — kV
75/85
Load Impedance
≥20kΩ
Opening speed (6 mm after contact separation) — m/s
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productHexing
HXV8
12 kV outdoor pole-mounted vacuum circuit breaker with sensors
Temperature range
-40℃~70℃
Auxiliary and Control Circuit — Rated Supply Voltage — V
DC: 24 or Other
Energy Harvesting Sensor — Rated Primary Input Voltage — kV
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details