HXM3E-250 – Smart metering circuit breaker with communication, 250 A

Smart metering circuit breaker with communication, 250 A

Miniature Circuit Breakers

  • 250 A
  • 2500 V
  • -40°C ~ 75°C
  • 165 × 131 × 96
Manufacturer part number
SMART-METERING-SWITCH
Manufacturer
Hexing
Rated Current In (A)
250 A
Storage Environment
-40°C ~ 75°C

Hexing HXM3E-250 smart circuit breaker combining protection, metering and communication for distribution protection in 380/400/415 V AC networks, rated 250 A.

Product overview

Hexing HXM3E-250 smart circuit breaker. The Hexing HXM3E-250 is a smart circuit breaker that integrates communication, metering, protection, control and edge computing in a single unit, intended for distribution protection in AC networks.

Main characteristics. Rated current In of 250 A, rated operating voltage 380/400/415 V AC, rated insulation voltage Ui of 1000 V and rated impulse withstand voltage Uimp of 8 kV. Rated ultimate short-circuit breaking capacity Icu of 50 kA and rated service short-circuit breaking capacity Ics of 36 kA. Breaking class L and utilization category A.

Metering and clock accuracy. Class 0.5S metering module with a voltage and current accuracy of 0.5%. Daily clock error of 0.5 s or less at the reference temperature of 23 °C, with continuous operation for over 5 years after a power failure.

Connectivity. HPLC, Bluetooth and RS485 communication, supporting the DL/T 645 and DL/T 698.45 protocols to report current, voltage, power, energy and product lifespan data to terminal devices.

Power and environment. Normal long-term operating temperature range of -40 °C to 70 °C, storage temperature of -40 °C to 75 °C, power frequency withstand voltage of 2500 V.

Typical uses. Protection of lines and power supply equipment, detection and monitoring of the load side, and provision of data for energy efficiency systems.

Integration. Outline dimensions 165 × 131 × 96 mm, mounting with 4 holes of 5 mm on a 126 × 35 mm pattern. Available on quotation from Atlas Electronics.

See all specifications

Highlights

  • Breaking Class: L
  • Main Technical Specifications: Specifications
  • Mounting Dimensions (mm): 126 × 35 (4 × φ5 holes)
  • Operating Temperature: Normal long-term operating temperature range: -40°C ~ 70°C
  • Outline Dimensions (mm) (L × W × H): 165 × 131 × 96
  • Power Frequency Withstand Voltage (V): 2500 V

Good to know before integrating

  • Thermal: rated operating range Normal long-term operating temperature range: -40°C ~ 70°C — check it against the installation environment.

See also

Technical questions

Ask a question

No published question about this part yet. Questions are reviewed before publication.

Request a quote