The HCDSP3-1500 is a three-pole T1+2 DC surge protection device protecting photovoltaic inverters and combiner boxes against lightning and switching surges.
Operating Temperature Range-40°℉+158°℉(-40℃+70℃)
Lightning discharge current(10/350us)6.25kA
Maximum discharge current (8/20μS)40kA
Nominal discharge current (8/20us)20kA
Short-circuit current rating2000A
Total discharge current(10/350 μs)12.5KA
Product overview
Overview. The HIITIO HCDSP3-1500 T1+2 is a DC surge protection device designed for photovoltaic and DC power systems exposed to direct lightning and switching surges. It complies with IEC 61643-31, EN 61643-31 and GB/T 18802-31.
Main characteristics. Maximum continuous operating DC voltage of 1500 V, with 600 V, 1000 V and 1200 V variants in the HC-PV series. Total discharge current of 40 kA (8/20 μs) and lightning discharge current of 12.5 kA (10/350 μs). Voltage protection level of 5200 V maximum between DC+ and DC- and earth. Short-circuit current rating of 2000 A. High-energy MOV protecting component with thermal protection.
Interfaces and connectivity. Protected modes (DC+)-PE, (DC-)-PE and (DC+)-(DC-). Maximum terminal wire cross-section of 35 mm² for flexible or rigid wire and 16 AWG (1.5 mm²) for rigid wire. End screw torque of 4.5 Nm. Working status and failure indication by green and red indicator, optional communication contact (RC).
Power and environment. Operating temperature range from -40 °C to +70 °C, allowable working humidity from 5 % to 95 %, altitude from -500 m to 2000 m. Thermoplastic housing with UL94 V0 flame-extinguishing class, IP20 protection for internal installation. Mounts on a 35 mm DIN rail according to EN 60715.
Typical uses. Protection of photovoltaic inverters and junction boxes, battery energy storage systems, DC distribution and control cabinets, renewable energy and microgrid installations, EV charging infrastructure.
The HCDSP3-1500 is a three-pole T1+2 DC surge protection device protecting photovoltaic inverters and combiner boxes against lightning and switching surges.
Operating Temperature Range-40°℉+158°℉(-40℃+70℃)
Lightning discharge current(10/350us)6.25kA
Maximum discharge current (8/20μS)40kA
Nominal discharge current (8/20us)20kA
Short-circuit current rating2000A
2. Datasheet extract (recorded values)
Parameter
Value
Response time
<25ns
AC/DC switching capability
AC:250V/0.5A; DC:250V/0.1A; 125V/0.2A; 75V/0.5A
Accord with a standard
GB/T 18802-31
Allowable workinghumidity
5%…95%
Atmospheric pressure and altitude
80kPa…106kPa/-500m…2000m
Communication contact(RC)
Optional
End screw torque
39.9 lbf·in [4.5 Nm]
HC-PV serise
600 1000 1200 1500
IEC/EN/UL Category
Level 1+2/ Type 1+2
Install
35 mm DINguide rail, According to EN 60715
Lightning discharge current(10/350us)
6.25kA
Maximum continuous operating DC voltage(DC+)-PE,(DC-)-PE (DC)-(DC-)
Voltage protection level (DC+) – PE,(DC-)-PE (DC)- (DC-)
≤2200V ≤4000V ≤4200V ≤5200V
Working status/failure indication
Green/Red
Integration
Points to check before using HCDSP3-1500 in a design. They are derived from the recorded characteristics, not from the manufacturer's application circuits.
1Thermalrated operating range -40°℉+158°℉(-40℃+70℃) — check it against the installation environment.
Power and communication
Lightning discharge current(10/350us)
6.25kA
Maximum continuous operating DC voltage(DC+)-PE,(DC-)-PE (DC)-(DC-)
600V 1000V 1200V 1500V
Maximum discharge current (8/20μS)
40kA
Nominal discharge current (8/20us)
20kA
Operating DC voltage
Choose an option 1000V 1200V 1500V 600V Clear
Short-circuit current rating
2000A
Total discharge current(10/350 μs)
12.5KA
Total discharge current(8/20 μS)
40KA
Voltage protection level (DC+) – PE,(DC-)-PE (DC)- (DC-)
≤2200V ≤4000V ≤4200V ≤5200V
Check the exact pin assignment and the application circuit in the datasheet, or ask our experts.
Implementation checklist
Thermal : rated operating range -40°℉+158°℉(-40℃+70℃) — check it against the installation environment.
Applications and use cases
Architectures in which HCDSP3-1500 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Solar panels produce most when nobody is home, and the surplus goes to the grid. A battery with its inverter stores this energy and returns it in the evening, with a meter measuring what the home draws
To check
Panel power and the inverter compatibility of the battery
Usable capacity compared with the evening and night consumption
Local grid connection rules for balcony and home systems
Solar production, storage and charging points on one site are often managed separately. Inverters, batteries, MPPT controllers, meters and chargers form a local energy system that shares production between users
To check
Regulatory framework for collective self-consumption in the country
Energy management system steering storage and charging
Metering accuracy for sharing between participants
Associated system blocks
ProductionStorageMeteringCharging
Need a complete solution?
Send a request for HCDSP3-1500 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productHIITIO
HCDSP3-1500
1500 V T1+2 DC surge protection device for PV systems