Hollysys AF-EMF8E electromagnetic energy meter for measuring energy and volume in hot and chilled water heating or cooling systems.
Temperature range4 to 95ºC
Temperature Difference Range3 to 70 K
AccuracyGrade 2
CommunicationMODBUS/HART
ConnectionFlange/wafer/threaded/clamp
Converter Protection ClassIP65/IP67
Product overview
Overview. The Hollysys AF-EMF8E electromagnetic energy meter is a Grade 2 energy meter combining an electromagnetic sensor, two PT1000 temperature sensors and an integrated energy calculator. It measures energy and volume in heating and cooling systems.
Main characteristics. The sensor covers diameters DN10 to DN2000 and a medium temperature range of 4 to 95 ºC, with a maximum medium temperature of 180 ºC. The temperature difference range is 3 to 70 K. The meter can operate as a flow meter, cold meter or heat/cold meter and measures forward and reverse flow rate as well as cold and heat power. Configured parameters and measured data are kept in permanent EEPROM memory.
Interfaces and connectivity. Communication is via MODBUS or HART, with a 4 to 20 mA or passive pulse output. The BACnet protocol is also supported. Bluetooth communication allows easy inspection and maintenance.
Power and environment. Power supply 220 V AC or 24 V DC. Protection class IP65/IP67 for the converter and IP65/IP67/IP68 for the sensor. Integrated or split structure.
Construction. Electrode in 316L, PU or PTFE lining, carbon steel flanges (304, 316 or 316L optional), carbon steel enclosure (304, 316 or 316L optional). Grounding by electrode or grounding ring. Connection by flange, wafer, threaded or clamp.
Typical uses. Energy audit and energy metering on chilled and hot water networks. The MODBUS/HART outputs allow connection to a supervision or control system.
Hollysys AF-EMF8E electromagnetic energy meter for measuring energy and volume in hot and chilled water heating or cooling systems.
Temperature range4 to 95ºC
Temperature Difference Range3 to 70 K
AccuracyGrade 2
CommunicationMODBUS/HART
ConnectionFlange/wafer/threaded/clamp
2. Datasheet extract (recorded values)
Parameter
Value
Accuracy
Grade 2
Communication
MODBUS/HART
Connection
Flange/wafer/threaded/clamp
Converter Protection Class
IP65/IP67
Diameter
DN10 to DN2000
Grounding Element
Grounding electrode/grounding ring
lining material
PU/PTFE
Material (Electrode)
316L
Material (Enclosure)
Carbon Steel (304/316/316L is optional)
Material (Flange)
Carbon Steel (304/316/316L is optional)
Medium temperature
To 180ºC
Output signal
4 to 20 mA/passive pulse
Power supply
220 V AC/24 V DC
Sensor protection class
IP65/IP67/IP68
Structure
Integrated type/split type
Temperature Difference Range
3 to 70 K
Temperature Measuring Element
PT1000
Temperature range
4 to 95ºC
Applications and use cases
Architectures in which AF-EMF8E can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
A building’s energy, comfort and occupancy data sit in separate systems. Sensors, meters and gateways feed one model of the building, room by room, to compare scenarios and steer the installations
To check
Data model and building plans available
Software platform hosting the twin
Sensor density needed for a useful model
Associated system blocks
SensorsMetersGateways
Need a complete solution?
Send a request for AF-EMF8E and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productHollysys
AF-EMF8E
Electromagnetic Energy Meter for Hot and Chilled Water
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details