UEC1-09C
Three-pole power contactor 9 A AC-3 50/60 Hz coil

- Hold-in Power Consumption in VA
- 9.5 VA 50/60 Hz (at 25 °C)
- Minimum Switching Current
- 0.1A for signalling circuit
- Mounting Support
- Screw; 35mm DIN Rail
- Number of Units in Package 1
- 1 pcs
Three-pole power contactor 9 A AC-3 50/60 Hz coil
The Hongfa UEC1-09C is a three-pole NO power contactor for switching motors and AC loads up to 690 V.
Overview. The Hongfa UEC1-09C is a three-pole (3 NO) power contactor from the UEC1 series. It switches AC loads with a rated operational voltage (Ue) of up to 690 V AC 50/60 Hz on the power circuit.
Main characteristics. Rated operational current of 9 A (≤ 60 °C) in AC-3 at 400 V and 25 A (≤ 60 °C) in AC-1 at 690 V for the power circuit. Auxiliary contacts in a 1NO1NC composition for the signalling circuit, with a conventional thermal current of 10 A (≤ 60 °C). Electrical durability of 1.2 million cycles at 9 A AC-3 and mechanical durability of 10 million cycles.
Coil and power consumption. AC 50/60 Hz control circuit without built-in suppressor module. Inrush power of 75 VA and hold-in power of 9.5 VA at 25 °C. Control voltage range of 0.8 to 1.1 Us between -40 and 60 °C.
Motor ratings and connectivity. Motor power rating of 2.2 kW at 220/230 V and 4 kW at 380/400 V in AC-3, and 5.5 kW at 660/690 V. Screw clamp terminals, power circuit tightening torque of 1.5 N·m. Mounting by screw or on a 35 mm DIN rail.
Environment and compliance. Operating ambient temperature from -40 to 60 °C, operating altitude up to 3000 m without derating, IP20 front face protection per IEC 60529, overvoltage category III. Conforms to IEC/EN 60947-4-1 and IEC/EN 60947-5-1 and certified CE, UKCA, VDE and UL (cULus).
Integration. Compatible with the CA1R, CA1S and CA1M 38 circuit breakers from the range. Suitable for controlling three-phase asynchronous motors in an electrical cabinet built to IEC standards.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for UEC1-09C, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 25 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO1NC,2NO2NC,other combinations can be customized |
| Average Impedance | 2.7 mΩ - Ith 50 Hz for power circuit |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Voltage Limits | 0.8...1.1 Us (-40…60 °C): operational AC 50 Hz; 0.85...1.1 Us (-40…60 °C): operational AC 60 Hz; 1...1.1 Us (60…70 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…70 °C): drop-out AC 50/60 Hz |
| Control Dircuit Type | AC at 50/60 Hz standard |
| Conventional Free Air Thermal Current [Ith] | 25 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Depth | 96 mm |
| Device Short Name | UEC1-09C |
| Electrical Durability | 1.2 M cycles 9 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 90 mm |
| Hold-in Power Consumption in VA | 9.5 VA 50/60 Hz (at 25 °C) |
| Inrush Power in VA | 75 VA 50/60 Hz (at 25 °C) |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| Maximum Operating Rate | Electrical: 750 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 10 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 1 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 1 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 1 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 2 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 3 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 5 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 7.5 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 2.2 kW at 220/230 V AC 50/60 Hz (AC-3); 4 kW at 380/400 V AC 50/60 Hz (AC-3); 5.5 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm DIN Rail |
| Net weight | 0.42 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 30 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...22 ms closing, 4...19 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...19 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 10.4 cm |
| Package 1 Length | 9.5 cm |
| Package 1 Weight | 0.48 kg |
| Package 1 Width | 5.0 cm |
| Package 2 Height | 25.0 cm |
| Package 2 Length | 32.5 cm |
| Package 2 Weight | 14.40 kg |
| Package 2 Width | 29.0 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL (cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC1 |
| Rated operational current (Ie) | 9 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 25 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Rated Operational Voltage (Ue) | Power circuit: ≤ 690 V AC 50/60Hz |
| Rated Short-Time Withstand Current [Icw] | 105 A ≤40 °C - 10 s for power circuit; 210 A ≤40 °C - 1 s for power circuit; 30 A ≤40 °C - 10 min for power circuit; 61 A ≤40 °C - 1 min for power circuit |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 13 lb.in(1.5 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 13 lb.in(1.5 N·m)- on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 11 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 11 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 42 48 110 115 127 220 230 240 380 400 415 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 45 mm |
No specification matches.
Last verification : 2026-11-02
Official documents and the technical data recorded for UEC1-09C. For a missing document or a specific revision, our experts send it to you.
The Hongfa UEC1-09C is a three-pole NO power contactor for switching motors and AC loads up to 690 V.
| Parameter | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 25 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO1NC,2NO2NC,other combinations can be customized |
| Average Impedance | 2.7 mΩ - Ith 50 Hz for power circuit |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Voltage Limits | 0.8...1.1 Us (-40…60 °C): operational AC 50 Hz; 0.85...1.1 Us (-40…60 °C): operational AC 60 Hz; 1...1.1 Us (60…70 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…70 °C): drop-out AC 50/60 Hz |
| Control Dircuit Type | AC at 50/60 Hz standard |
| Conventional Free Air Thermal Current [Ith] | 25 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Depth | 96 mm |
| Device Short Name | UEC1-09C |
| Electrical Durability | 1.2 M cycles 9 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 90 mm |
| Hold-in Power Consumption in VA | 9.5 VA 50/60 Hz (at 25 °C) |
| Inrush Power in VA | 75 VA 50/60 Hz (at 25 °C) |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| Maximum Operating Rate | Electrical: 750 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 10 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 1 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 1 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 1 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 2 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 3 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 5 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 7.5 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 2.2 kW at 220/230 V AC 50/60 Hz (AC-3); 4 kW at 380/400 V AC 50/60 Hz (AC-3); 5.5 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm DIN Rail |
| Net weight | 0.42 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 30 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...22 ms closing, 4...19 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...19 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 10.4 cm |
| Package 1 Length | 9.5 cm |
| Package 1 Weight | 0.48 kg |
| Package 1 Width | 5.0 cm |
| Package 2 Height | 25.0 cm |
| Package 2 Length | 32.5 cm |
| Package 2 Weight | 14.40 kg |
| Package 2 Width | 29.0 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL (cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC1 |
| Rated operational current (Ie) | 9 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 25 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Rated Operational Voltage (Ue) | Power circuit: ≤ 690 V AC 50/60Hz |
| Rated Short-Time Withstand Current [Icw] | 105 A ≤40 °C - 10 s for power circuit; 210 A ≤40 °C - 1 s for power circuit; 30 A ≤40 °C - 10 min for power circuit; 61 A ≤40 °C - 1 min for power circuit |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 13 lb.in(1.5 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 13 lb.in(1.5 N·m)- on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 11 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 11 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 42 48 110 115 127 220 230 240 380 400 415 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 45 mm |
Answers to the questions that the recorded characteristics of UEC1-09C can answer. A question is not asked when nothing is recorded to answer it.
Yes — recorded under "Auxiliary Contact Composition": 1NO1NC,2NO2NC,other combinations can be customized.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Three-pole power contactor 9 A AC-3 50/60 Hz coil




Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | UEC1-09C |
| Manufacturer | Hongfa |
Power Contactors
1 Pole + Shunt 20A-40A Definite Purpose Contactor · Ref. : SA-1.5P
Price on request
Power Contactors
Three-pole power contactor 38 A AC-3 AC coil 50/60 Hz
Price on request
Power Contactors
Technical article: relay versus contactor differences
Price on request
Power Contactors
EPS box with integrated contactors for 1-phase/3-phase inverters · Ref. : X1/X3-EPS
Price on request
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details