UEC1-32C
3-pole power contactor 32 A AC-3 AC 50/60 Hz coil

- Hold-in Power Consumption in VA
- 9.5 VA 50/60 Hz (at 25 °C)
- Minimum Switching Current
- 0.1A for signalling circuit
- Mounting Support
- Screw; 35mm DIN Rail
- Number of Units in Package 1
- 1 pcs
3-pole power contactor 32 A AC-3 AC 50/60 Hz coil
The Hongfa UEC1-32C is a 3-pole 32 A power contactor rated for AC-3 duty, used to switch motors and loads on AC 50/60 Hz circuits up to 690 V.
Overview. The Hongfa UEC1-32C power contactor is a 3-pole contactor from the UEC1 series, designed to switch AC power circuits up to 690 V. It is supplied with a pole contact composition of 3 NO and auxiliary contacts of 1 NO+1 NC.
Main characteristics. Rated operational current of 32 A at 60 °C in AC-3 up to 400 V and 50 A in AC-1 up to 690 V. Conventional free air thermal current of 50 A for the power circuit and 10 A for the signalling circuit. Electrical durability of 1.0 million cycles at 32 A AC-3 with Ue ≤ 400 V and mechanical durability of 10 million cycles. Maximum operating rates of 600 cycles/h electrical and 3600 cycles/h mechanical.
Coil and control. AC 50/60 Hz control circuit without built-in suppressor module. Inrush power of 75 VA and hold-in power of 9.5 VA at 25 °C. Control voltage limits of 0.8 to 1.1 Us at -40…60 °C for AC 50 Hz and 0.85 to 1.1 Us for AC 60 Hz. Control voltages available from 24 V to 415 V AC.
Connection and environment. Screw clamp terminals with a tightening torque of 2.5 N·m on the power circuit and 1.2 N·m on the control circuit. Mounting by screw or on 35 mm DIN rail. Degree of protection IP20 on the front face. Ambient operating temperature of -40 to 60 °C, operating altitude up to 3000 m without derating, overvoltage category III and rated impulse withstand voltage of 6 kV.
Typical uses. Control of three-phase and single-phase motors, with AC-3 motor ratings of 7.5 kW at 220/230 V, 15 kW at 380/400 V and 18.5 kW at 660/690 V. Suited to control and power cabinets fitted with IEC contactors.
Standards and certifications. Conforms to IEC/EN 60947-4-1 and IEC/EN 60947-5-1, as well as GB/T 14048.4 and GB/T 14048.5. Certified CCC, CE, UKCA, VDE and UL (cULus). RoHS and REACh compliant.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for UEC1-32C, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 50 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO1NC,2NO2NC,other combinations can be customized |
| Average Impedance | 2 mΩ - Ith 50 Hz for power circuit |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Voltage Limits | 0.8...1.1 Us (-40…60 °C): operational AC 50 Hz; 0.85...1.1 Us (-40…60 °C): operational AC 60 Hz; 1...1.1 Us (60…70 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…70 °C): drop-out AC 50/60 Hz |
| Control Dircuit Type | AC at 50/60 Hz standard |
| Conventional Free Air Thermal Current [Ith] | 50 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Depth | 100 mm |
| Device Short Name | UEC1-32C |
| Electrical Durability | 1.0 M cycles 32 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 92.5 mm |
| Hold-in Power Consumption in VA | 9.5 VA 50/60 Hz (at 25 °C) |
| Inrush Power in VA | 75 VA 50/60 Hz (at 25 °C) |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| Maximum Operating Rate | Electrical: 600 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 10 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 2 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 5 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 5 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 10 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 10 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 20 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 25 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 7.5 kW at 220/230 V AC 50/60 Hz (AC-3); 15 kW at 380/400 V AC 50/60 Hz (AC-3); 18.5 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm DIN Rail |
| Net weight | 0.47 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 30 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...22 ms closing, 4...19 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...19 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 11.1 cm |
| Package 1 Length | 9.9 cm |
| Package 1 Weight | 0.50 kg |
| Package 1 Width | 5.0 cm |
| Package 2 Height | 26.4 cm |
| Package 2 Length | 33.7 cm |
| Package 2 Weight | 15.30 kg |
| Package 2 Width | 29.0 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL(cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC1 |
| Rated operational current (Ie) | 32 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 50 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Rated Operational Voltage (Ue) | Power circuit: ≤ 690 V AC 50/60Hz |
| Rated Short-Time Withstand Current [Icw] | 260 A ≤40 °C - 10 s for power circuit; 430 A ≤40 °C - 1 s for power circuit; 60 A ≤40 °C - 10 min for power circuit; 138 A ≤40 °C - 1 min for power circuit |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 22 lb.in(2.5 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 22 lb.in(2.5 N·m)- on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 42 48 110 115 127 220 230 240 380 400 415 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 45 mm |
No specification matches.
Last verification : 2026-11-02
Official documents and the technical data recorded for UEC1-32C. For a missing document or a specific revision, our experts send it to you.
The Hongfa UEC1-32C is a 3-pole 32 A power contactor rated for AC-3 duty, used to switch motors and loads on AC 50/60 Hz circuits up to 690 V.
| Parameter | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 50 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO1NC,2NO2NC,other combinations can be customized |
| Average Impedance | 2 mΩ - Ith 50 Hz for power circuit |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Voltage Limits | 0.8...1.1 Us (-40…60 °C): operational AC 50 Hz; 0.85...1.1 Us (-40…60 °C): operational AC 60 Hz; 1...1.1 Us (60…70 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…70 °C): drop-out AC 50/60 Hz |
| Control Dircuit Type | AC at 50/60 Hz standard |
| Conventional Free Air Thermal Current [Ith] | 50 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Depth | 100 mm |
| Device Short Name | UEC1-32C |
| Electrical Durability | 1.0 M cycles 32 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 92.5 mm |
| Hold-in Power Consumption in VA | 9.5 VA 50/60 Hz (at 25 °C) |
| Inrush Power in VA | 75 VA 50/60 Hz (at 25 °C) |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| Maximum Operating Rate | Electrical: 600 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 10 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 2 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 5 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 5 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 10 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 10 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 20 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 25 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 7.5 kW at 220/230 V AC 50/60 Hz (AC-3); 15 kW at 380/400 V AC 50/60 Hz (AC-3); 18.5 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm DIN Rail |
| Net weight | 0.47 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 30 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...22 ms closing, 4...19 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...19 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 11.1 cm |
| Package 1 Length | 9.9 cm |
| Package 1 Weight | 0.50 kg |
| Package 1 Width | 5.0 cm |
| Package 2 Height | 26.4 cm |
| Package 2 Length | 33.7 cm |
| Package 2 Weight | 15.30 kg |
| Package 2 Width | 29.0 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL(cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC1 |
| Rated operational current (Ie) | 32 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 50 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Rated Operational Voltage (Ue) | Power circuit: ≤ 690 V AC 50/60Hz |
| Rated Short-Time Withstand Current [Icw] | 260 A ≤40 °C - 10 s for power circuit; 430 A ≤40 °C - 1 s for power circuit; 60 A ≤40 °C - 10 min for power circuit; 138 A ≤40 °C - 1 min for power circuit |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 22 lb.in(2.5 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 22 lb.in(2.5 N·m)- on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 42 48 110 115 127 220 230 240 380 400 415 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 45 mm |
Answers to the questions that the recorded characteristics of UEC1-32C can answer. A question is not asked when nothing is recorded to answer it.
Yes — recorded under "Auxiliary Contact Composition": 1NO1NC,2NO2NC,other combinations can be customized.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
3-pole power contactor 32 A AC-3 AC 50/60 Hz coil




Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | UEC1-32C |
| Manufacturer | Hongfa |
Power Contactors
1 Pole + Shunt 20A-40A Definite Purpose Contactor · Ref. : SA-1.5P
Price on request
Power Contactors
Three-pole power contactor 38 A AC-3 AC coil 50/60 Hz
Price on request
Power Contactors
Technical article: relay versus contactor differences
Price on request
Power Contactors
EPS box with integrated contactors for 1-phase/3-phase inverters · Ref. : X1/X3-EPS
Price on request
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details