UEC3-32N
3-pole 32 A contactor, AC 50/60 Hz coil

- Average Hold-in Power Consumption in VA
- 10.5 VA 50/60 Hz (at 25 °C)
- Minimum Switching Current
- 0.1A for signalling circuit
- Mounting Support
- Screw; 35mm DIN Rail
- Number of Units in Package 1
- 1 pcs
3-pole 32 A contactor, AC 50/60 Hz coil
Hongfa UEC3-32N 3-pole contactor for switching power loads, rated 32 A in AC-3 at 400 V with an AC 50/60 Hz control coil.
Overview. The Hongfa UEC3-32N is a 3-pole contactor from the UEC3 series, designed for switching power circuits in AC-3, AC-4 and AC-1 utilisation categories.
Main characteristics. Rated operational current of 32 A at 400 V AC in AC-3, 26.7 A in AC-4 and 50 A in AC-1 at 690 V; conventional free air thermal current of 50 A; rated insulation voltage of 690 V conforming to IEC 60947-4-1; rated impulse withstand voltage of 6 kV. Auxiliary contact composition of 1 NO and 1 NC. Electrical durability of 0.9 million cycles at 32 A AC-3 and mechanical durability of 10 million cycles.
Motor power. 7.5 kW at 220/230 V, 15 kW at 380/400 V and 18.5 kW at 660/690 V in AC-3 for three-phase motors, with horsepower ratings for 110 to 600 V networks.
Coil and consumption. AC 50/60 Hz control coil without built-in suppressor module, operational from 0.85 to 1.1 Us at -40…60 °C. Average hold-in consumption of 10.5 VA and inrush of 75 VA at 25 °C.
Connection and mounting. Screw clamp terminals, tightening torque of 2.0 N·m on the power circuit and 1.2 N·m on the control circuit. Mounting by screw or on 35 mm DIN rail. Degree of protection IP20 front face conforming to IEC 60529.
Operating conditions. Operation from -40 to 60 °C, altitude up to 3000 m without derating, overvoltage category III. Dimensions 56 x 85.5 x 80 mm, net weight 0.38 kg.
Typical uses. Control of motors and power loads in electrical cabinets, according to the utilisation categories listed.
Standards and certifications. Conforming to IEC/EN 60947-4-1 and IEC/EN 60947-5-1, CE, UKCA, CCC and UL (cULus) marked, RoHS and REACH conforming.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for UEC3-32N, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 50 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO,1NC |
| Average Hold-in Power Consumption in VA | 10.5 VA 50/60 Hz (at 25 °C) |
| Average Impedance | 2.7 mΩ - Ith 50 Hz for power circuit |
| Average Inrush Power in VA | 75 VA 50/60 Hz (at 25 °C) |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Type | AC at 50/60 Hz standard |
| Control Circuit Voltage Limits | 0.85...1.1 Us (-40…60 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…60 °C): drop-out AC 50/60 Hz |
| Depth | 80 mm |
| Device Short Name | UEC3-32N |
| Electrical Durability | 0.9 M cycles 32 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 85.5 mm |
| [Icw] Rated Short-time Withstand Current | 260 A ≤40 °C - 10 s for power circuit; 138 A ≤40 °C - 1 min for power circuit; 60 A ≤40 °C - 10 min for power circuit |
| [Ie] Rated Operational Current | 32 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 26.7 A (at ≤60 °C) at ≤ 400 V AC AC-4 for power circuit; 50 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| [Ith] Conventional Free Air Thermal Current | 50 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Maximum Operating Rate | Electrical: 600 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 10 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 2 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 5 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 5 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 10 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 10 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 20 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 25 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 7.5 kW at 220/230 V AC 50/60 Hz (AC-3); 15 kW at 380/400 V AC 50/60 Hz (AC-3); 18.5 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm DIN Rail |
| Net weight | 0.38 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 30 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...22 ms closing, 4...22 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...22 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 9.6 cm |
| Package 1 Length | 8.8 cm |
| Package 1 Weight | 0.48 kg |
| Package 1 Width | 6.3 cm |
| Package 2 Height | 225 cm |
| Package 2 Length | 33.0 cm |
| Package 2 Weight | 13.2 kg |
| Package 2 Width | 28.5 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA, UL (cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC3 |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 18 lb.in (2.0 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 18 lb.in (2.0 N·m)- on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ue]Rated Operational Voltage | Power circuit: ≤ 690 V AC 50/60Hz |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 48 110 220…230 380 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 56 mm |
No specification matches.
Last verification : 2026-11-02
Official documents and the technical data recorded for UEC3-32N. For a missing document or a specific revision, our experts send it to you.
Hongfa UEC3-32N 3-pole contactor for switching power loads, rated 32 A in AC-3 at 400 V with an AC 50/60 Hz control coil.
| Parameter | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 50 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO,1NC |
| Average Hold-in Power Consumption in VA | 10.5 VA 50/60 Hz (at 25 °C) |
| Average Impedance | 2.7 mΩ - Ith 50 Hz for power circuit |
| Average Inrush Power in VA | 75 VA 50/60 Hz (at 25 °C) |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Type | AC at 50/60 Hz standard |
| Control Circuit Voltage Limits | 0.85...1.1 Us (-40…60 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…60 °C): drop-out AC 50/60 Hz |
| Depth | 80 mm |
| Device Short Name | UEC3-32N |
| Electrical Durability | 0.9 M cycles 32 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 85.5 mm |
| [Icw] Rated Short-time Withstand Current | 260 A ≤40 °C - 10 s for power circuit; 138 A ≤40 °C - 1 min for power circuit; 60 A ≤40 °C - 10 min for power circuit |
| [Ie] Rated Operational Current | 32 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 26.7 A (at ≤60 °C) at ≤ 400 V AC AC-4 for power circuit; 50 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| [Ith] Conventional Free Air Thermal Current | 50 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Maximum Operating Rate | Electrical: 600 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 10 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 2 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 5 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 5 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 10 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 10 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 20 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 25 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 7.5 kW at 220/230 V AC 50/60 Hz (AC-3); 15 kW at 380/400 V AC 50/60 Hz (AC-3); 18.5 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm DIN Rail |
| Net weight | 0.38 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 30 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...22 ms closing, 4...22 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...22 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 9.6 cm |
| Package 1 Length | 8.8 cm |
| Package 1 Weight | 0.48 kg |
| Package 1 Width | 6.3 cm |
| Package 2 Height | 225 cm |
| Package 2 Length | 33.0 cm |
| Package 2 Weight | 13.2 kg |
| Package 2 Width | 28.5 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA, UL (cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC3 |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 18 lb.in (2.0 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 18 lb.in (2.0 N·m)- on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 10.7 lb.in (1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ue]Rated Operational Voltage | Power circuit: ≤ 690 V AC 50/60Hz |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 48 110 220…230 380 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 56 mm |
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
3-pole 32 A contactor, AC 50/60 Hz coil




Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | UEC3-32N |
| Manufacturer | Hongfa |
Power Contactors
1 Pole + Shunt 20A-40A Definite Purpose Contactor · Ref. : SA-1.5P
Price on request
Power Contactors
Three-pole power contactor 38 A AC-3 AC coil 50/60 Hz
Price on request
Power Contactors
Technical article: relay versus contactor differences
Price on request
Power Contactors
EPS box with integrated contactors for 1-phase/3-phase inverters · Ref. : X1/X3-EPS
Price on request
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details